Procedure:
1. At the ADDRESS control, set the left and right rotary switch as specified for the device in the corresponding
system.
2. Set the terminator at the TERM slider as specified for the device in the corresponding system.
Also see:
• Setting Option for Address and Terminator ⇒ page 93
• Defaults for Addresses and Terminators ⇒ page 93
9.4.6

Commissioning an Individual Battery Cabinet

Performing system registration
To complete commissioning, a system registration must be performed
• Use the following link for the system registration: https://my.sma-service.com/.
Requirements:
☐ The inverter has been correctly mounted and connected.
☐ The inverter enclosure cover is securely closed.
☐ The battery has been correctly mounted and connected.
☐ The battery cabinet is securely closed.
☐ The supplied energy meter has been correctly mounted and connected.
Procedure:
1. If a SMA Data Manager is available, activate the SMA Data Manager (see manual for the SMA Data Manager).
2. Press the external switch on the outside of the cabinet door.
3. Press the SWITCH control element on the battery management system.
4. Activate the display on the battery management system. To do this, tap with the fingers on the highlighted area
beside the display.
☑ The battery management system display shows the number of battery modules detected.
5. If the number of battery modules detected does not match the
number of battery modules installed, disconnect the battery from
the voltage source Disconnecting from voltage sources and check
all battery communication connections.
6. If the number of battery modules detected is still incorrect after eliminating any battery communication faults,
contact Service.
7. If the number of battery modules detected matches the number of battery modules installed, confirm the correct
number of battery modules. To do this, tap with the fingers on the highlighted area beside the display.
8. Activate the next menu item. To do this, tap with the fingers on the highlighted area beside the display.
☑ The display shows the installed firmware version and the assigned IP address.
9. Check that the installed firmware version begins with 55.xx.