Chapter 3 Web Configuration Page

Editing the Group Register
Modbus
Register: The Modbus Register number for the ET-6000 module
Alias: A string that describes the Modbus register. It can be a reference to a tag in the image
of the Web editing page which is selected from the "Page properties" section. (If the tag of the
Modbus register has defined on the image)
Scaling: The Modbus register value will be divided by the scale value before being displayed
on the web page, or multiplied before value is written to the ET-6000 module.
This function is only used for Input or Holding register types.
Enable: Enable the Scaling function
Disable: Disable the Scaling function.
Example:
1.
Modbus register value= 620, Scale value=10
2.
Modbus register value=7325, Scale value=1000
page.
3.
Web page input= 32.20, Scale value=100
register.
Register
Type: Defines the Modbus register type.
Bit format: Coil (Digital Output), Discrete input (Digital Input).
Byte format: Input (Analog Input), Holding (Analog Output).
Data
Type: Defines the data type of the Modbus register and must be either Input or Holding.
The data type can be one of the following:
Data Type
Unsigned 16
Signed 16
Unsigned 32
Signed 32
ET-6000 User's Manual, 2007, Sep., V1.1,
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru

Table 3-5 Input or Holding Data Types

Definition
A 16-bit positive value
A16-bit value with a sign
A 32-bit positive value. The Most significant word (register) is on the
low address.
A 32-bit value with sign. The Most significant word (register) is on the
low address.
62.0 will be shown on the Web page.
7.325 will be shown on the Web
3220 will be written to the Modbus