ICP DAS USA ET-6000 Series User Manual page 93

Table of Contents

Advertisement

ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ
Chapter 3 Web Configuration Page

Modbus Registers and Factory Defaults
Common Functions
Modbus
Points
Address
40557
1
DI Module Functions
Modbus
Points
Address
(Max.)
00350
1
00351~
80
00431
40200~
32
40231
DO Module Functions
Modbus
Points
Address
(Max.)
00435~
80
00514
00515~
80
00594
ET-6000 User's Manual, 2007, Sep., V1.1,
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
Description
Set host watch dog timer
(Second)
Description
Enable all DI latched
status (high/low)
Enable low speed
(100Hz) digital counter
Preset value for low
speed (100Hz) digital
counter
Description
Power on value for DO
Safe value for DO
Range
5~65535 (Enable)
(<5: Disable)
Range
0 (Disable)
1(Enable)
0 (Disable)
1(Enable)
0~65535
Range
0=off
1=on
0=off
1=on
6PH-002-11----------91 
Factory
default
0 (Disable)
Factory
default
0 (Disable)
0 (Disable)
0
Factory
default
0
0