Q3: How are the local registers mapped to the polled data in a MDC-700?

A3: Only the function code 01/02/03/04 can be used in the polling definition section
01: Read Coil Status (Read DO)
02: Read Input Status (Read DI)
03: Read Holding Registers (Read AO)
04: Read Input Registers (Read AI)
Refer to the example below,
# UseComPort SlaveModbusID FunctionCode RegStart
*
1
*
1
*
2
*
2
*
2
*
2
The MDC-700 will sort the order of polling data by COM port number and the sequence of polling
definition; and then map the local registers corresponding to the data type (DI/DO/AI/AO) by the
order of polling data. So the data comes from different slave devices with the same type will be
saved in continuous registers, and a Modbus mater device and read the data on a variety of slave
devices with one Modbus command.
COM1
Read DO: 000000:000007
Read DI: 100000:100007
Copyright © 2014 ICP DAS Co., Ltd. All Rights Reserved. ∗ E-mail: service@icpdas.com
1
1
1
2
3
4
COM2
Read DO: 000000:000003
Read DI: 100000:100003
Read AO: 400000:400003
Read AI: 300000:300003
RegCount
Addr
1
0
8
2
0
8
1
0
4
2
0
4
3
0
4
4
0
4
Timeout
Preset
EventProcess
Value
2
0
2
0
2
0
2
0
2
0
2
0
Read DO
000000:000007
000008:000011
Read DI
100000:100007
100008:100011
Read AO
400000:400003
Read AI
300000:300003
- 48 -