Mode 1: Modbus/RTU
Enable the protocol converter function to convert Modbus/TCP to Modbus/RTU. In
Modbus/RTU mode, the COM port can only connect to Modbus/RTU slave devices.
Mode 2: System Reserved
Mode 3: UpLink
Enable the COM port as a Modbus/RTU slave port.
Mode 4: Debug port
The Modbus kernel displays some messages while communicating with Modbus
clients or masters.
Mode 5: Console
This is a serial console port that can be used to configure the module via an RS232.
Net
ID:
If the Modbus station number in a Modbus/TCP request (from PC or HMI) matches the Net
ID, the request is passed to the Modbus kernel. Then Modbus kernel program will then
respond and send the internal registers to the Modbus/TCP client (PC or HMI). The content
of all other registers is zero.
Time out:
It's used for Modbus protocol communication via a RS232 interface. After completing data
transmission, the system begins to count time, if timeout expires, the system stop receiving
responses.
Stations per COM
This value is used to decide how many Modbus/RTU stations can add on one ET-6000
COM port for control.
Settings
Baud Rate
Data Bit
Parity
Stop Bit
Checksum
Operation Mode
ET-6000 User's Manual, 2007, Sep., V1.1,
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
port:

Table 3-2 Serial Port Settings

Range
300, 600, 1200, 2400, 4800, 9600,
19200, 38400,57600,115200 bps
7, 8 bit
None, Even, Odd
1, 2 bit
True, False
0~5
Factory default
115200 bps
8
None
1
False
5 (Console mode)