ET6060 (D) I/O Specifications:
Digital Output
Output Channels
LED Indicator
Output Type
Operating Voltage Range
Relay Contact Voltage Range
Max. Load Current
Max. Operate Time
Max. Release Time
Insulation Resistance
Dielectric Strength
Surge Strength
Relay Life
Digital Input
Input Channels
LED Indicator
Input Type
On Voltage Level
Off Voltage Level
Input Impedance
Counters
Intra-module Isolation, Field to
Logic
ET-6000 User's Manual, 2007, Sep., V1.1,
8
Yes
Power Relay, Form A (Normal Open)
5 ~ 240VAC (47~63Hz)
5 ~ 24VDC
0~ 250VAC (47~63Hz)
0~ 28VDC
3.0 A/Channel
15
Max.
milliseconds
3
Max.
milliseconds
Min. 1,000 MOhms, at 500VDC
Between Open Contacts: 750VAC 50/60Hz (at 1 Minute)
Between Coil and Contacts: 4,000VAC 50/60Hz (at 1
Minute)
10,000V (at 1.2*50us)
Mechanical: 10 million operations at no Load Condition
Electrical: 100, 000, 28VDC@5A min. , Resistive
10 (Sink/ source)
Yes
Isolation, Two Common for All Digital Inputs
+10V ~ 50V
+3V max
10K Ohms, 0.66W
Channels: 10
Max. Input Frequency: 100Hz
Min. Pulse Width: 5ms
3750V rms