Installation; Voltage Input; Current Input - ICP DAS USA PM-3033 Series Quick Start Manual

Hide thumbs Also See for PM-3033 Series:

Advertisement

3.

Installation

Please use the soft dry clothes to clean the instrument.
Please do not use any chemical or detergent or volatile solvents to clean the instrument, in order to avoid any
possibility of the cover damage.
Dimension: 127mm(length)× 33mm(wide)× 100mm(high)
Please read this operation manual carefully before using.
Please re-confirm the measure position.
Reconfirm the RST (ABC) phase sequence of the power system.
PM-3033 series can be installed as rail mounting mode or embedded, no need to drill a hole or screw to fix it
(rail mounting width can up to the length of 35 mm).
Meter auxiliary power for PM-3033 series is DC +12V ~+48V.

3.1. Voltage Input

1.
PM-3033 series: Input Voltage up to 500V.
For any higher Input Voltage large than 500V, please add the PT (power transformer), and Change PT RATIO
setup.
2.
Confirm the RST (ABC) phase sequence.

3.2. Current Input

1. CT with secondary side output 1A/5A can be connected directly.
2. The current direction must follow K-L marked on CT's.
800A/5A Primary CT Installation and Wiring
ICP DAS Co., LTD
PM-3033 series Quick Start V1.10
Page 2