ICP DAS USA ET-6000 Series User Manual page 164

Table of Contents

Advertisement

ГК Атлант Инжиниринг – официальный представитель в РФ и СНГ
Appendix D: Modbus Register
Table
(4xxxx) AO address
Begin
Points
address
555
1
CPU reset status
556
1
CPU reset events
557
1
Set host watch dog timer
558
1
Host WDT events
559
1
Module name
563
1
Module nick name
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
Description
ET-6000 User's Manual, 2007, Sep., V1.1,
Registers
Range
per Point
1
1= by power on
2= by 0.8 second WDT
3= by Reset command
1
How many CPU reset
events has happened?
When CPU is reset by
one of the situations
described in register
555, the event
increases one count.
1
<5: Disabled 5~65535:
Enabled (unit: second)
(default=0)
When ET-6000 loses
communication with PC
more than the WDT
setting, DO and AO go
to their safe values and
host WDT events plus
1 count.
1
How many host WDT
events has happened
after CPU reset?
4
8 ASCII characters
8
16 ASCII characters
6PH-002-11----------162 
Access
Type
R/W
R/W/E
R/W/E
R/W
R
R/W/E

Advertisement

Table of Contents
loading