Chapter 3 Web Configuration Page

3.5

I/O Pair Connection

The function is used to make a DI to DO pair through the Ethernet. The communication is
based on Modbus/TCP. Once the configuration is done, the ET-6000 can poll Remote DI
status and then write to a local DO device constantly in the background.
Settings
I/O Pair
Enable/Disable I/O pair connection
connection
Remote IP
IP address of remote device
Remote TCP port
TCP listen port of remote device
Remote Net ID
Modbus Net ID of remote device
Connection
Timeout to build a connection.
timeout
Reconnect
Continue to attempt to reconnect to the
interval
remote module once the connection is
lost until the reconnection time has
expired.
Scan time
Time period to establish the
communication
Communication
Timeout for Modbus/TCP
timeout
communication.
Local
DO
base
DO base address of local DO register
address
that will be mapped to remote DI device.
Remote DI base
DI base address of remote DI device
address
that will be mapped to local DO register.
I/O count
I/O count mapped from the base
address
ET-6000 User's Manual, 2007, Sep., V1.1,
+7(495)109-02-08 sales@bbrc.ru www.bbrc.ru
Table 3-8 I/O Pair Connection Settings
Description
Range
Enable, Disable
0~ 42949672965 ms 0
0~65535
0~255
0~ 42949672965 ms 5000 ms
0~ 42949672965 ms 10000 ms
0~ 42949672965 ms 1000 ms
0~ 42949672965 ms 500 ms
Depend on the ET-
6000
Depend on remote
device
1~255
6PH-002-11----------115 
Default
Disable
502
1
0
0
0