3.2.5 Installing Optional Components

3.2.5.1 Installing a Battery Grounding Failure Detector

Prerequisites
Procedure
Step 1 Remove the top cover from the power unit, and remove the bracket of the battery
grounding failure detector.
Issue 10 (2023-05-26)
If the power units share battery strings, you need to install a battery
grounding failure detector only in power unit 1.
If the power units do not share battery strings, you need to install battery
grounding failure detectors in both power units.