Item
Altitude (m)
Top outlet fan If the fan unit is configured,
Air filter
maintenance
period (d)
Intra-rack
power
module start
delay (s)
Inter-rack
power
module start
delay (s)
Maintenance
bypass
cabinet
Intelligent
detection
module
BCB trips if
UPS stops
power supply
Issue 10 (2023-05-26)
Description
Set this parameter based on
the altitude of the place
where the rack is used.
set this parameter to Enable.
Specifies the rack air filter
maintenance interval. If it is
set to 0, there is no reminder.
These two parameters enable
the UPS to control the
interval that each rack (or
module) transfers from
battery mode to normal
mode, which reduces the
impact on the generator or
power grid. In the case of
battery undervoltage, the
system automatically
shortens the delay for
transferring to normal mode
to 1/8 of the normal delay to
accelerate the transfer and
prevent battery
overdischarge. The start
delay of a module in a rack
varies depending on the rack
number and module number.
#1 module in rack 1 does not
have a start delay.
If the maintenance bypass
unit is configured, set this
parameter to Enable.
N/A
Indicates whether the BCB
trips when the system stops
supplying power and the
output power is off.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
≤ 1000
≤ 1000, 1000–
2000, 2000–
3000, 3000–
4000, 4000–
5000
Disable
Disable,
Enable
0
0–365
1.0
0.5–120.0
5
2–120
Disable
Disable,
Enable
Disable
Disable,
Enable
Enable
Disable,
Enable
132