UPS5000-S-1200 kVA
User Manual
Item
Output freq.
track rate
(Hz/s)
Bypass Settings
Figure 4-29 Bypass settings
Issue 10 (2023-05-26)
Description
This parameter can be
adjusted based on site
requirements. If Output freq.
track rate (Hz/s) is slow, the
inverter frequency is different
from the bypass frequency
when the bypass frequency
changes. If output is
overloaded or the inverter is
faulty, an interruption (less
than 20 ms) occurs when the
UPS transfers from normal
mode to bypass mode. If
Output freq. track rate
(Hz/s) is fast, the inverter
frequency is unstable.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0.6
0.1 to 2.0
135