Table 2-5 Indicator description
Indicator
NORMAL
ALM
FAULT
Functions
Specifications
Issue 10 (2023-05-26)
Color
Green
Yellow
Red
As a control interface for the entire system, the ECM communicates with each
module and provides a bus to communicate with the dry contact card. The
ECM ensures equalized output currents between modules so that load power
is equally shared.
Provides module running information for the MDU.
Controls the running of a single UPS5000, and reports the UPS5000 status
information to other monitoring modules.
The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack
parallel CAN communication.
Hot-swappable
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
The BSC port is used in a dual-bus system to
synchronize output frequencies and phases between
UPS systems, ensuring that two buses can switch
with each other.
BSC cables are hot-swappable.
Status
Description
Steady on
This ECM is the active ECM.
Blinking at 0.5
This ECM is the standby ECM and it
Hz
is ready.
Off
This ECM is not ready or the CPLD of
this ECM is being upgraded.
Blinking at 4
The DSP of the ECM is being
Hz
upgraded or not configured.
Steady on
The ECM has a minor alarm, but it
does not need to be replaced.
Off
The ECM has no minor alarm or the
DSP of the ECM is being upgraded.
Steady on
The ECM has a critical alarm.
Off
The ECM has no critical alarm or the
DSP of the ECM is being upgraded.