Item
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Harmonic current
Table 8-5 Bypass input electrical specifications
Item
System
Rated voltage
Rated frequency
Frequency range
Input mode
Issue 10 (2023-05-26)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
At 0–40°C: not derated when the voltage is 187–280 V
AC; derated to 35% load when the voltage is 187–80 V
AC.
50/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz
50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6
Hz, ±2 Hz by default)
The mains input and bypass input share a power
source or use different power sources.