UPS5000-S-1200 kVA
User Manual
Output Settings
Figure 4-28 Output settings
Item
Output
voltage level
Output volt.
adjustment
(V)
Output
frequency
(Hz)
Issue 10 (2023-05-26)
Description
Specifies the system output
voltage level. This parameter
is configurable only after the
inverter shuts down. After
you change the voltage level,
the upper limit of the bypass
voltage restores to the
default value. (If the voltage
level is 380 V or 400 V, the
default upper limit is +15%.
If the voltage level is 415 V,
the default upper limit is
+10%.)
The output voltage can be
slightly adjusted based on
the onsite power distribution
condition to ensure a
minimum difference between
the output voltage and the
bypass voltage and facilitate
uninterruptible power supply
when the UPS transfers from
normal mode to bypass
mode.
Specifies the system output
frequency level.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
400
380, 400, 415
The default
380 V: 209.0–
value is 220.0,
231.0
230.0, and
400 V: 218.5–
240.0 when
241.5
the voltage
415 V: 228.0–
level is 380 V,
252.0
400 V, and 415
V respectively.
50
50, 60
134