Huawei UPS5000-S-1200 kVA User Manual page 157

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Battery Maintenance
● Perform battery maintenance when no alarm is active on the UPS. Otherwise,
● A proportion of battery capacity will discharge during battery maintenance.
● Do not perform battery maintenance when a D.G. is connected.
Perform battery maintenance periodically to increase the battery lifespan and
improve the UPS reliability. Battery maintenance includes Forced Equalized
Charging, Shallow Dis. Test, and Capacity Test. The next maintenance time
displayed on the screen indicates the upcoming time in which to check batteries.
Figure 4-41 Battery maintenance (lead-acid battery)
Figure 4-42 Battery Maint. (lithium battery)
Item
Forced Equalized Charging
Issue 10 (2023-05-26)
NO TICE
the UPS may supply no power.
This reduces the discharge time before the next charge.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Forcibly perform equalized charging on batteries.
4 User Interface
149