Annual Maintenance - Huawei UPS5000-S-1200 kVA User Manual

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Battery voltage
Shallow discharge test
(recommended)

6.2.4 Annual Maintenance

Table 6-6 Annual maintenance
Item
Capacity Test
Issue 10 (2023-05-26)
Expected Result
When the UPS is backed up,
discharge a battery to the
undervoltage alarm threshold,
to refresh the capacity of the
battery.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
● Equalized charging
voltage: 2.35 V/cell
±0.02 V/cell
● Float charging voltage:
2.25 V/cell ±0.02 V/cell
Conduct a shallow
discharge test when the
UPS is backed up to verify
that the batteries can
discharge normally.
6 Routine Maintenance
Troubleshooting
1. Check whether the
equalized charging
voltage and float
charging voltage of a
battery are normal.
2. If the charging voltage
of a battery exceeds the
specifications
requirement, perform a
complete forcible
equalized charging for
the battery, and check
again whether the
voltage is normal.
3. If the fault persists,
contact Huawei
technical support.
1. If the batteries cannot
discharge normally,
locate the fault (for
abnormal alarms, see
the alarm list).
2. If the fault persists,
contact Huawei
technical support.
Troubleshooting
1. Locate the cause when an
exception is identified.
2. If the fault persists, contact
Huawei technical support.
211