Starting The Inverter - Huawei UPS5000-S-1200 kVA User Manual

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Step 2 (Optional) On the LCD of the system, choose System Info > Settings > DST
Settings and set the DST mode as required.
Step 3 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. If there is
any other alarm, you need to rectify the fault.
Step 4 If the system has connected to the remote EPO switch, you need to choose
Monitoring > Param. Settings > System Settings on the WebUI and check that
EPO detection is set to Enable.
Step 5 View the system running diagram on the MDU to check that the UPS is working in
bypass mode.
----End

5.1.3 Starting the Inverter

Starting the UPS on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End
Starting the UPS on the WebUI
Step 1 Open a browser (Internet Explorer 11 for example) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
then click OK.
Step 3 In the address box of the browser, enter https://
Issue 10 (2023-05-26)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair.
● After you set network parameters, connect the UPS to the network over a network
cable, which enables you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Setting. Check that System Capacity, Power module capacity, Requisite
modules, and Redundant modules match the actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
contacts Set and check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.