UPS5000-S-1200 kVA Quick Guide
Issue: 08
Part Number: 31509942
Date: 2020-12-15
1
Overview
Model
Weight
Dimensions (H x W x D)
1. Before installation, read the user manual carefully to get familiar with product information
and safety precautions.
2. Use insulated tools during installation and operation.
3. Only engineers certified by Huawei or its agents are allowed to install, commission, and
maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS
faults caused are beyond the warranty scope of Huawei.
UPS5000-S-1200KVA-FP
2360 kg
2200 mm x 2800 mm x 1000 mm
Power unit 2
Power unit 1
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
Bypass unit
Input and output unit
1

Advertisement

loading

Summary of Contents for Huawei UPS5000-S-1200

  • Page 1 2. Use insulated tools during installation and operation. 3. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults caused are beyond the warranty scope of Huawei.
  • Page 2: Installing The Ups

    (1) Surge protective box (2) Control module (3) Monitor control module (4) Power modules (5) Surge protective device (6) Mains input circuit breaker (SPD) and SPD switch of power unit 1 (Q1-1) (7) Mains input circuit breaker of (8) Bypass input switch (Q2) (9) Output circuit breaker of power unit 2 (Q1-2) power unit 1 (Q5-1)
  • Page 3 Recommended Channel Steel Dimensions Combining the Power Units and Bypass Unit 1. Remove the side panel of the bypass unit.
  • Page 4 2. Combine the power units and bypass unit in the following sequence: bottom, top, and middle. 3. Install the side panels removed from the bypass unit to power unit 2. 4. Secure the UPS. (A) Mounting holes on the channel steel: M12x60 bolts (B) Mounting holes on the floor: M12x60 expansion bolts Bolts are not included.
  • Page 5 Installing Busbars • Before handling a busbar, wear protective gloves to avoid getting injured by sharp edges. Move a busbar with caution to avoid scratching cabinets. • • Each busbar weighs about 50 kg. Be cautious to avoid injury when moving heavy objects. Preparation: two scaling ladders that are more than one meter high At least two persons are required to carry a busbar.
  • Page 6 3. Install busbar components (numbered 02 and 03). Before installation, remove the screws that are partially tightened from the busbar component. Busbar Component (numbered 03) Busbar component (numbered 02) 4. Use copper bars (numbered 04–06) to connect the busbar components (numbered 02 and 03). Before installation, remove the screws that are partially tightened from the busbar component.
  • Page 7 6. Install the left sealing plate (numbered 08). 7. Install the side sealing plate (numbered 09) for the input and output unit. 8. Install the right sealing plate (numbered 10).
  • Page 8 9. Install the rear sealing plate (numbered 11) for the power unit. 10.Install sealing plates (numbered 12) for the bypass unit and input and output unit. 11.Install supports for the busbar covers.
  • Page 9: Installing Cables

    12.Install sealing plates for the battery wiring protective covers. 13.Install mounting plates. Mounting plate Power unit 2 Input and Power unit 1 Bypass unit plate output unit plate plate plate (numbered 13) 14.Install the top busbar covers. Installing Cables UPS Cable Connection Reference...
  • Page 10 • Prepare cables away from the cabinets to prevent scraps from falling inside. Cable scraps may ignite and cause personal injury or device damage. • After cables have been installed, clean the cabinets in a timely manner. Keep the cabinets and surrounding environment clean and tidy.
  • Page 11 Distances Between Top Copper Bars (unit: mm) Copper Bar Specifications (unit: mm)
  • Page 12 Copper Bar Positions Equipotential ground point Battery UPS Output Main Bypass Input Battery Input Input Port Description Connection Method Bolt Specifications Bolt Length Torque Mains input Crimped DT terminals M12 35 mm 47 N· m Bypass input Crimped DT terminals M12 35 mm 47 N·...
  • Page 13 4. Install supports and covers on the top of the protective covers for each power unit. 5. Before power-on, remove the protective covers from the top of the power units. 6. Connect the signal cables between the power units and the bypass unit.
  • Page 14 7. Only if the system is in 1+1 parallel configuration (skip this step if the system is a single UPS or dual-bus system), remove ECM 1 and ECM 2 from each control module of power unit 1, power unit 2, and bypass unit of each UPS, remove the J3 and J6 jumper caps from each ECM, and reinstall the ECMs in the control modules.
  • Page 15: Verifying The Installation

    Turn on output circuit breaker Q5-1 and Q5-2. Turn on mains input circuit breaker Q1-1, Q1-2 and bypass input switch Q2. After the UPS is powered on, initialization begins. The monitoring display unit (MDU) displays the Huawei logo and an initialization progress bar.
  • Page 16 Initial Startup • If the UPS is powered on for the first time, you need to obtain the startup password from the Service Expert app. Skip this step if the UPS is not powered on for the first time. The Service Expert app can be downloaded from Google Play Store and can run on Android. •...
  • Page 17 2. Set the language, time, date, network parameters, and system parameters on the Settings Wizard screen. 3. After you perform the settings, the Bypass mode and No battery alarms are reported by the MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
  • Page 18: Shutting Down The Ups

    Default User Preset Password 000001 admin (administrator) Changeme 000001 operator (common user) Changeme browser (browsing user) Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker.
  • Page 19 • Shutting down the inverter on the WebUI. On the system WebUI, choose Monitoring > Control, and click Inv. OFF. After confirmation, the inverter is shut down. Powering Off a Single UPS Turn off the system output switch (Q5). Turn off mains input circuit breaker 1 (Q1-1), mains input circuit breaker 2 (Q1-2), bypass input switch (Q2), output circuit breaker 1 (Q5-1), and output circuit breaker 2 (Q5-2) of the UPS.
  • Page 20 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: https://support.huawei.com/enterprise https://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...