Step 6 On the RCCMD client, you can view messages through the View Event Log at the
upper left corner.
----End

4.2.5.3 UPS Alive Check Function

Context
Whether the RCCMD SSL encrypted transmission is enabled on the WebUI of
UPS5000 MDU and RCCMD client is irrelevant to the heartbeat detection function.
Only when the SSL encryption is enabled on the RCCMD client, the logs recorded
by the RCCMD client are marked with "(SSL...)".
On the RCCMD client, the IP address of the MDU that detects heartbeat needs to
be added. Then the UPS alive check function is supported; the RCCMD can check
whether the UPS and RCCMD communicate properly; the RCCMD can receive
messages sent by the MDU.
Procedure
Step 1 On the RCCMD client, add the IP address of the MDU that detects heartbeat, as
shown in
Step 2 The UPS5000 MDU supports both ways of heartbeat detection. If the job
configured for the MDU event is set to RCCMD TRAP, the RCCMD client needs to
be set to by the use of CS121/UPSMAN Traps. If by polling CS121/UPSMAN
every x seconds... is selected as the method of detecting heartbeats, set the
detection method. The default interval is 1800s and detection is performed 100
times, as shown in