  • Page 1 UPS5000-S-1200 kVA User Manual Issue Date 2019-06-25 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    User Manual About This Document About This Document Purpose This document describes the UPS5000-S-1200 kVA in terms of its features, performance, working principles, appearance as well as instructions for installation, and operation and maintenance (O&M). Intended Audience This document is intended for: ...
  • Page 4 Added the optional fan unit. Issue 03 (2019-04-02) Updated descriptions of installing communications cables. Issue 02 (2019-01-26) Updated the busbar installation sequence. Issue 01 (2018-05-30) This issue is the first official release. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    2.3.5 Control Module ................................ 23 2.3.5.1 Overview ................................23 2.3.5.2 ECM..................................24 2.3.5.3 Dry Contact Card ..............................26 2.3.5.4 Monitoring Interface Card ............................ 28 2.3.6 MDU ..................................33 2.4 Typical configurations ..............................35 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 4.1.1 Main Menu ................................90 4.1.2 Menu Hierarchy ............................... 92 4.1.3 System Info ................................95 4.1.3.1 Running ................................95 4.1.3.2 Alarms ................................... 99 4.1.3.3 Settings ................................101 4.1.3.4 Maintenance ................................ 124 4.1.3.5 About .................................. 127 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.6.1 Forced Equalized Charging Test ..........................171 5.6.2 Shallow Discharge Test ............................172 5.6.3 Capacity Test................................173 5.6.4 Test Data Download ............................... 174 5.7 Transferring to Maintenance Bypass Mode ......................175 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 6.2.4 Annual Maintenance .............................. 185 7 Troubleshooting ........................186 8 Technical Specifications ......................189 9 (Optional) TN-C System Application ................... 194 10 Alarm List ..........................195 11 Acronyms and Abbreviations ....................206 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Safety Precautions

    Follow the precautions and special safety instructions provided by Huawei when operating Huawei products. Huawei will not be liable for any consequences that are caused due to violations regarding general safety regulations and equipment design, production, and usage safety standards.
  • Page 10 Personal Requirements Only Huawei engineers or engineers certified by Huawei are allowed to perform UPS commissioning and maintenance. Otherwise, human injury or equipment damage may occur, and any resulting UPS faults will be beyond warranty scope.
  • Page 11: Electrical Safety

    The personnel who install the AC facility must be qualified to perform high voltage and AC operations.  When selecting, connecting, and routing power cables, ensure compliance with local laws and regulations. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 12 Backfeed Protection Dry Contact The UPS can be configured with a backfeed protection dry contact to work with an external automatic circuit breaker, preventing the voltage from flowing back to input terminals over Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 13 Otherwise, short circuits will occur and may result in serious injury or death.  If any liquid is detected inside the product, immediately disconnect the power supply and contact the administrator. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: Operating Environment

    1.4 Battery Safety This section describes precautions for operating batteries. Before operating batteries, carefully read the safety precautions to ensure correct battery handling and connection is performed, and personal safety is managed. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 1 Safety Precautions  To ensure battery safety and efficient battery management, use the batteries delivered with the UPS. Huawei shall not be responsible for battery damage caused by using non-Huawei batteries for Huawei UPSs.  Ensure lead-acid battery handling is in accordance with local regulations.
  • Page 16: Mechanical Safety

    If any personnel are exposed to battery electrolyte, wash the exposed area with clean water immediately and seek medical advice if the situation is serious. 1.5 Mechanical Safety Moving Sharp Objects Wear protective gloves when moving sharp objects. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 17: Laying Out Cables

    Figure 1-2 Tilting angle of a cabinet Handling Fans Do not insert fingers or boards into the operating fans until the fans are switched off, and have stopped running. 1.6 Laying Out Cables Binding Signal Cables Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Information About Foreign Objects Near Ups Equipment Installation

    Huawei UPS uses the highest safety standard in equipment design to ensure that live parts are not in contact with the exterior and that no foreign object will enter the equipment during operation.
  • Page 19 UPS5000-S-1200 kVA User Manual 1 Safety Precautions manager to ensure that no foreign object enters the UPS modules/units or relevant auxiliary equipment/components. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Overview

    Output capacity 1200 kVA Solution FusionPower The maximum capacity of UPS5000-S-1200 kVA-FP is 1200 kVA and it is compatible with a capacity of 1100 kVA, 990 kVA, 880 kVA, 770 kVA and 660 kVA. 2.2 Working Principle  indicates an input mode.
  • Page 21: Conceptual Diagram

    In normal mode, the rectifier converts AC power into DC power, then the inverter converts DC power into high-precision AC outputs. The conversions protect loads from interference such as input harmonics, glitches, and voltage transients. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 22: Bypass Mode

    UPS which means it may be affected by mains outage, and incorrect AC voltage or frequency. Figure 2-4 UPS conceptual diagram in bypass mode Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Battery Mode

    The maintenance bypass unit has been installed. When the UPS works in maintenance bypass mode, the current flows through the maintenance bypass instead of the power module. You can maintain the circuit inside the cabinet. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Eco Mode

    ECO voltage range, the UPS transfers from bypass mode to normal mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries using a charger. The ECO mode delivers a high efficiency. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Joint Power Mode

    In this case, the power module obtains energy from both the mains and batteries, and the energy is converted into AC outputs over the inverter. Figure 2-8 Conceptual diagram in joint power mode Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Product Introduction

    UPS5000-S-1200 kVA User Manual 2 Overview 2.3 Product Introduction 2.3.1 Appearance Figure 2-9 UPS (1) Power Unit 1 (2) Power Unit 2 (3) Bypass Unit (4) Input and output Unit Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Product Structure

    1 (Q5-1) breaker 2 (Q5-2) module (13) Bypass control (14) System output module switch (Q5) Modules in each power unit are numbered in ascending order, that is, module 1…, and module n. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Power Module

    (blinking at 0.2 Hz, on for 2.5s and off for 2.5s). Blinking at short The module is not configured, the intervals inverter or rectifier DSP software is being upgraded, or the inverter Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 29 Specifications  Dimensions (H x W x D): 130 mm x 442 mm x 620 mm  Weight: < 34 kg  Rated output capacity: 55 kVA/55 kW Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Bypass Module

    Blinking at short The bypass is not configured or the intervals DSP software is being upgraded (blinking at 4 Hz, on for 0.125s and off for 0.125s). The bypass CPLD software is being Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Control Module

    (from left to right). The four cards are hot swappable. One subrack is reserved above the dry contact card. A backfeed protection card or dry contact extended card can be inserted into this subrack. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 32: Ecm

    Ports are protected by a security mechanism. 2.3.5.2 ECM Appearance The control module consists of two energy control modules (ECMs) in active/standby mode. Figure 2-14 ECM Table 2-4 Ports on the ECM Silk Screen Description Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 33  The system provides three types of CAN communication: monitoring CAN communication, intra-rack parallel CAN communication, and inter-rack parallel CAN communication. Specifications  Hot-swappable  1 U high Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Dry Contact Card

     12 V: battery circuit breaker trips. switch tripped BCB_0V Port for signal ground EPO_NO In use: Reserved Emergency power-off If the normally open Disconnected (EPO) port (NO) port is Controls Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 35 Set the EPO port to NO or NC as required.  Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m, its cross-sectional area must be 0.5 mm to 1.5 mm Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Monitoring Interface Card

    DO_1 to DO_4 meet the maximum voltage and current requirements of 30 V DC/1 A or 60 V DC/0.5 A. Table 2-7 Description of ports on the monitoring interface card Port Silk Bypass Power Description Screen Unit Unit Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 37 DB26 Provides FE, RS485, I2C, and CAN signals. Battery B_TEMP Reserved temperature sensor port Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 38 Figure 2-17 Figure 2-18 are recommended wiring methods for DO ports. Figure 2-17 Wiring method 1 Figure 2-18 Wiring method 2 Figure 2-19 COM1 pins Table 2-8 COM1 pin definition Description Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 UPS5000-S-1200 kVA User Manual 2 Overview Description RS485– RS485+ 12V_PORT Figure 2-20 COM2 pins Table 2-9 COM2 pin definition Description RS485+ RS485– RS485+ RS485– CANH0 CANL0 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then connect it to RS485+. Twist cables to pin 2 and pin 5 into one cable and then connect it to RS485–. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 41: Mdu

    Yellow A minor alarm has been generated, and the buzzer buzzes at 2 Hz. Green The UPS is running properly or a warning has been generated. The MDU is powered off. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 CAN communication build-out resistor in a parallel system Functions The monitor display unit (MDU) allows for general UPS operations, parameter setting, viewing of running status and alarms, and so on. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 43: Typical Configurations

    Energy control modules (ECMs) on each UPS are connected over parallel cables. The parallel connections synchronize the UPS outputs to supply power to loads. If one UPS fails, the other UPSs continue supplying power to loads. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Single Ups Dual-Bus System

    (BSC). The UPS systems work in normal mode or bypass mode. The conceptual diagram uses a dual-bus system with a single UPS as an example. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 45: Optional Components

    -BXA001 BBB box  PDU8000-1250DCV8 Converges the energy from PDU8000-(0630, 1250, 2000) -BGA001 multiple battery strings. DCV8-BGA001 BBB Box User Manual  PDU8000-2000DCV8 -BGA001 iBattery Collects battery information. It Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 46 The ECM expansion subrack does not support onsite installation. If you require this optional component, inform Huawei when you purchase the UPS so that Huawei can install the subrack before delivery. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 47: Installation

    The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA batteries) are 20–30° C. Operating temperatures higher than 30° C shorten the battery lifespan and operating temperatures lower than 20° C reduce the battery backup time. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Installation Clearances

    Insulate installation tools to prevent electric shocks. Prepare the following tools and meters indicated in Table 3-1 for installation. Table 3-1 Tools and meters Tools and Meters Electric pallet truck Manual pallet truck Ladder Rubber mallet Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 Level instrument Polyvinyl chloride Cotton cloth Label Electrician's knife (PVC) insulation tape Electrostatic Protective gloves Insulated gloves Insulation protective discharge (ESD) shoes gloves Torque screwdriver Cable cutter Brush Flat-head screwdriver (2–5 mm) Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Preparing Power Cables And Copper Bars

    3.1.3 Preparing Power Cables and Copper Bars The UPS can generate large leakage currents. A circuit breaker that provides leakage current protection is not recommended. Prepare wiring copper bars based on the following figures and current requirements. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 51 (1) The area marked by the line box is reserved for dense busway. (2) No power distribution box (PDB) or cabling is allowed inside the area marked by the line box. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 52 Table 3-2 Recommended cross-sectional areas for power cables Item Specifications Mains input Mains input current (A) 2420 Bypass input Bypass input current (A) 2000 Output Output current (A) 2000 Battery input Battery nominal discharge current (A) 3152 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 53 It is recommended that the AC power cable be no longer than 30 meters and the DC power cable be no longer than 50 meters. When connecting power cables, comply with the tightening torque listed in Table 3-3 ensure secure connections and prevent safety risks. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Unpacking

    If multiple loads are connected, specifications for branch circuit breakers must not exceed the recommended specifications.  The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to realize specific protection. 3.1.4 Unpacking Context Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Optional) Splitting The Bypass Unit And Input And Output Unit

    If the door of the power distribution equipment room is not wide enough to move the UPS, you can split the bypass unit and input and output unit before the movement. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 56 Step 3 Remove the PE, N, L1, L2 and L3 copper bars. Figure 3-6 Remove copper bars Step 4 Remove cable terminal, U, V and W copper bars and epoxy plate. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 Step 5 Remove the top, middle, and bottom connecting plates in sequence from the bypass unit and input and output unit. Use a step ladder to remove the top connecting plates as the cabinet is high. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Optional) Combining The Bypass Unit And Input And Output Unit

    Step 4 Check that the bypass unit and input and output unit are combined completely and securely. Step 5 After checking that cabinets are combined properly, reinstall the rear covers. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 59: Single Ups Installation

    Step 1 Determine the cabinet installation positions on the floor based on holes in the marking-off template for floor installation.  A: mounting holes on the channel steel  B: mounting holes on the floor Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 60 Figure 3-10 Dimensions for the holes for the bypass unit and input/output unit (unit: mm) Step 2 Use a hammer drill to drill holes for installing the expansion bolts and then install the expansion sleeves in the holes. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 61 Partially tighten the expansion bolt and vertically insert it into the hole. Hit the expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole. Partially tighten the expansion bolt. Remove the bolt, spring washer, and flat washer. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 62 Figure 3-13 Removing the side panel from the bypass unit Step 4 Combine the power units and bypass unit, and install the connecting plates in the following sequence: bottom, top, and middle. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 63: Channel Steel Installation

    Step 5 Use M12x60 expansion bolts to secure the power units, bypass unit, and input/output unit to the expansion bolt mounting holes on the floor in sequence. Step 6 Install anchor baffle plates. Figure 3-15 Installing anchor baffle plates ----End 3.2.1.2 Channel Steel Installation Prerequisites Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 64 UPS5000-S-1200 kVA User Manual 3 Installation  Huawei does not provide channel steel or expansion bolts used for securing channel steel.  Ensure that the surface of channel steels is smooth. Figure 3-16 Recommended channel steel dimensions (unit: mm) Procedure Step 1 Determine the cabinet installation positions on the channel steel based on holes in the marking-off template for channel steel installation.
  • Page 65: Installing Busbars

    2. Figure 3-18 Removing front panels and dustproof covers Step 2 Install the U-shaped sealing plate component (numbered 01). Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 Figure 3-20 Installing busbar component (1) Insulator (The two insulators do not need to be secured with screws.) Step 4 Install the busbar component (numbered 07) and secure it to the cabinet. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 Figure 3-21 Installing busbar component Step 5 Install the left sealing plate (numbered 08). Figure 3-22 Installing sealing plates Step 6 Install the side sealing plate (numbered 09) for the input and output unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 68 Figure 3-23 Installing sealing plates Step 7 Install the right sealing plate (numbered 10). Figure 3-24 Installing sealing plates Step 8 Install the rear sealing plate (numbered 11) for the power unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 69 Figure 3-25 Installing sealing plates Step 9 Install the sealing plates (numbered 12) for the bypass unit and input and output unit. Figure 3-26 Installing sealing plates Step 10 Install supports for the busbar covers. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Ups Cable Connection Reference

    Figure 3-27 Installing supports for the busbar covers Step 11 Install sealing plates for the battery wiring protective covers. Figure 3-28 Installing sealing plates for the battery wiring protective covers ----End 3.2.3 UPS Cable Connection Reference Context Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 71 Choose an appropriate cabling route based on the actual situation. The figure is for reference only. Step 4 Connect the cable with a crimped terminal to the corresponding copper bar. Step 5 Clean foreign matter inside the cabinet. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Connecting Cables

    Step 3 Connect input and output busbars and battery cables based on the top copper bar position diagram. Step 4 Connect the signal cables between the power units and bypass unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 Step 5 Connect the PARALLEL ports on the power units and bypass unit to form a loop by using parallel signal cables. Figure 3-33 Connecting the signal cables Step 6 Install supports and covers on the top of the protective covers. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 (1) Mounting plate (numbered 13) (2) Power unit 2 plate (2) Power unit 1 plate (4) Bypass unit plate (5) Input and output unit plate Step 8 Install the busbar covers. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 75: Installing Optional Components

    If the power units share battery strings, you need to install a battery grounding failure detector only in power unit 1.  If the power units do not share battery strings, you need to install battery grounding failure detectors in both power units. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 76 Connect the signal cable of the battery grounding failure detector to the dry contact card (MUE05A) of the control module of the power unit. Connect the transformer and battery grounding failure detector. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 77: Installing The Maintenance Bypass Unit

    Step 1 Determine the installation position for the maintenance bypass unit based on the cabinet securing holes in the marking-off template.  A: mounting holes on the channel steel  B: mounting holes on the floor Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Step 2 Remove the side panel and PC panel from the input and output unit, and remove the rear and front covers from the input and output unit and maintenance bypass unit. Step 3 Combine the maintenance bypass unit with the input and output unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 Figure 3-42 Installing connecting plates Step 4 Secure the maintenance bypass unit to the mounting surface. Step 5 Connect copper bars inside the maintenance bypass unit and input and output unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 Step 6 Install sealing plate supports and sealing plates for the maintenance bypass unit. Figure 3-44 Installing sealing plate supports and sealing plates Step 7 Install mounting plates for the maintenance bypass unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 81: Installing A Fan Unit

    Step 10 Reinstall the front and rear covers, and install the side panel removed from the input and output unit on the maintenance bypass unit. ----End 3.2.5.3 Installing a Fan Unit Configure the fan unit if you install the cabinet against the wall. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 82 Figure 3-47 UPS (1) Fan unit – left (2) Power unit 2 (3) Power unit 1 (6) Fan unit – right (4) Bypass unit (5) Input/output unit Figure 3-48 Fan unit structure Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 83 B: mounting holes on the floor Figure 3-49 Fan unit hole dimensions (unit: mm) Figure 3-50 Power unit hole dimensions (unit: mm) (1) This hole is not required when power unit 1 is installed. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 84 Figure 3-52 Removing the door header (rear view of the cabinet) Step 6 Install the fan unit accessories at the rear of the cabinet. Figure 3-53 Installing the fan unit accessories (rear view of the cabinet) Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 85 1, power unit 2, and fan unit. Install the screws that secure the cabinet to the ground. Figure 3-55 Installing the connecting kits (1) Connecting kits without floating nuts (2) Connecting kits with floating nuts Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 86 Step 1 Install the right sealing plate of the input/output unit. Figure 3-57 Install the right sealing plate Step 2 Remove the rear sealing plate from the power unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 87 Step 3 Install the rear sealing plate of the power unit. Figure 3-59 Installing the rear sealing plate of the power unit Step 4 Install the fan baffle plate (numbered 50). Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 88 (2) Part R (the part removed from the rear sealing plate of the power unit) Step 6 Install the front and rear sealing plates (numbered 12) of the bypass unit and input/output unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 89 The procedure for installing a cable for the fan unit and installing a mounting plate is different. For details about how to install cables for the power cabinet, bypass cabinet, and input/output bypass cabinet, see the preceding steps. Step 1 Install the cable of the fan unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 90 (4) Power unit 1 (numbered 13) mounting plate mounting plate mounting plate (7) Fan unit – right (5) Bypass unit (6) Input/Output unit (8) Right mounting mounting plate mounting plate mounting plate plate ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 91: Connecting Other Optional Components

    Dry contact Install in the control extended card module of the bypass unit. Backfeed protection Install in the control card module of the bypass unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 92: Remote Epo

    3 Installation 3.2.6 Remote EPO  Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG.  Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
  • Page 93: Parallel System Installation

    Step 2 Choose a parallel mode and connect cables to the parallel system based on site requirements. Figure 3-68 1+1 parallel system schematic diagram Connect power cables according to port silk screen. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 94: Connecting Signal Cables

    The power cables include bypass input power cables and UPS output power cables. ----End 3.3.2 Connecting Signal Cables Connecting Signal Cables to a Parallel System Figures show only the CM, which stands for the UPS. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 95: Installation Verification

    (4) Power Unit 2 of UPS2 (5) Power Unit 1 of UPS2 (6) Bypass Unit of UPS2 Connecting Other Signal Cables Connect signal cables for each UPS. 3.4 Installation Verification Table 3-7 lists check items. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 96 3. There is no foreign matter around switch terminals. 4. There is no foreign matter on the bottom plate of the cabinet. 5. There is no foreign matter on the rear module subrack. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 97 2. After verifying the installation, reinstall all the covers. 3. Do not remove the dustproof cover before power-on to prevent dust inside the UPS. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 98: User Interface

    Figure 4-1 Main menu Table 4-1 Main screen description Number Area Function Status bar Displays the UPS model, capacity, configuration, current date and time, USB flash drive status, and buzzer status. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 99 On the System Info screen of the system, you can tap the power unit or bypass unit as indicated in the following figure to access the monitoring screen for the power unit or bypass unit. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 100: Menu Hierarchy

    Load Battery System Info Runn Info AC Output UPS Load Mains Input Bypass Input Power Unit 1 Batt. Power Unit 2 Batt. Total Runtime Environment Data Alarms Active Alarms Historical Alarms Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 101 UPS Load Mains Input Inv. ON Inv. OFF Buzzer Off Historical Alarms Power Unit Power Unit Status Mains Load Battery Power Unit Info Runn Info AC Output UPS Load Mains Input Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 102 Bypass Unit Bypass Unit Status Bypass Load Bypass Unit Info Runn Info AC Output UPS Load Bypass Input Total Runtime Alarms Active Alarms Historical Alarms Maintenance ECM Switchover Fan Life About Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 103: System Info

    Module data of this power unit Battery Detailed Detailed battery data Data of this power unit On the System Info screen, tap to access the Runn Info screen of the system. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 104 On the System Info screen, tap the power unit icon to access the Power Unit N battery screen, and tap to access the Runn Info screen of the current power unit. Figure 4-5 Power unit running 1 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 Crest factor Proportion of the peak value of load current to the valid value. The UPS load of the power unit does not display the Load ratio. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 If no sensor is connected, NA is displayed.) Backup time (min) Battery backup time estimated at the current load Remaining cap. (%) Remaining battery capacity State of health Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 107: Alarms

    Active alarms of the power unit bypass unit Historical Alarms All historical alarms Historical alarms of Historical alarms of this power unit the bypass unit Buzzer Off Buzzer off Clear Faults Clearing all alarms Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 108 This screen displays alarm information including the severity, name, ID, location, and generation time. Figure 4-8 Active alarms Historical Alarms This screen displays alarm information including the severity, name, ID, location, generation time, and clear time. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 109: Settings

    Comm - Batt Temp Sensor Battery temperature sensor settings of this power unit Comm - BMU BMU settings of this power unit Comm - WiFi Settings System WiFi settings System Settings System settings Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 110 Battery settings of this power unit iBOX Settings iBOX settings of this power unit On the System Info screen, tap to access the Settings screen of the system. Figure 4-10 System settings 1 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 111 On the System Info screen, tap the power unit icon to access the Power Cabinet N Info screen, and tap to display the Settings screen of the current power unit. Figure 4-12 Power unit settings Communication Settings Figure 4-13 System communication settings Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 = 0. That is when the corresponding bits are both 1, the result is 1. In other cases, the result is Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 Specifies the Ethernet gateway. 192.168.0.1 1.0.0.0–223.255. 255.255 NAT mapping NAT means network address Disable Disable, Enable translation. If it is set to Disable, Internet cannot access IP addresses in the local area network (LAN). Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 114 Stop bit in the Modbus 1–2 communication frame format. When the UPS is connected over the serial port Modbus, set this parameter based on the frame format that the upstream device Modbus supports. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 115 Figure 4-18 Ambient temperature and humidity sensor Item Description Default Value Value Range Start address 32–44 Quantity Number of cascaded ambient 0–4 temperature and humidity sensors Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 116 Default Value Value Range Start address 16–28 Quantity Number of cascaded battery 0–4 temperature sensors Figure 4-20 BMU Item Description Default Value Value Range Start address Quantity Number of cascaded BMUs 0–12 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 117 USB port to MAC address identify the WiFi device to which the mobile phone is connected. Password The password for accessing Changeme WiFi. System Settings Figure 4-22 System settings 1 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 118 ± 8%, ± 9%, ± 10% voltage and the rated voltage is greater than this value, the system determines that the ECO voltage is abnormal and transfers Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 119 (s) the case of battery undervoltage, the system automatically shortens the delay for transferring to normal mode to 1/8 of the normal delay to accelerate the transfer and prevent battery Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 120 PDC. The UPS enters the D.G. mode when a D.G. is detected over dry contacts. D.G. power Set these two parameters to 800 kVA 0 kVA to 5000 limiting (kVA) control the valid input current Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 121 The default 380 V: adjustment (V) slightly adjusted based on the value is 220.0, 209.0–231.0 onsite power distribution 230.0, and 240.0 400 V: condition to ensure a minimum when the 218.5–241.5 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 +10%, +15%, voltage exceeds the upper +20%, and +25%. The default threshold for the bypass voltage, value is +15%. the system determines that the  When the voltage level is 400 V, Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 123 ECO frequency range. Battery Settings Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge time. When you set battery parameters, note the following: Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 Each battery has a nominal voltage of 2 V, 6 V, or 12 V.  In a 1+1 parallel system, two 1.2MW UPS systems cannot share the same battery string. Figure 4-28 Battery settings 1 Figure 4-29 Battery settings 2 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 125 If this parameter is set to 0, there is no reminder. Chg. cur. The charging current limit is a 0.1C10 0.05C10 to limiting coef. multiple of the battery capacity. 0.15C10 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 126 Shallow dis. Set the proportion of the 10%–50% test dis. ratio discharge capacity to the total discharge capacity. The value is configurable in any mode. iBOX Settings Figure 4-31 iBOX settings Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 127 Figure 4-33 Advanced parameters Item Description Default Value Value Range Current source Specifications of the Hall effect 200 A Hall sensor sensor used to detect iBOX 200A, Hall Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 128 Disable all the dry contacts for a dry contact card that is not connected and all the dry contacts that are not used to prevent false alarms.  ( ) encloses a unit, and [ ] encloses silk screen. Specify dry contact settings on the following cards: Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 129 Enable, the mains and bypass backfeed protection is enabled. MUS05A DO_1 Controls the status of DO ports on the MUS05A dry contact card. Action, MUS05A DO_2 Action, Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 130 DO on the MUE07A DO_3, MUE07A. MUE07A DO_4, MUE07A DO_5 MUE07A DI_1, Corresponds to the signal of the MUE07A DI_2, input dry contact DI on the MUE07A. MUE07A DI_3, MUE07A DI_4, MUE07A DI_5 Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 131 If the password complexity check Enable Disable, Enable complexity is disabled, the user password is check required to be a string of six to eight digits. If the password complexity check is enabled, the Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 132: Maintenance

    Fan Life Estimating the fan Estimating the fan life of the power life of the bypass modules in this power unit On the System Info screen, tap to display the Maintenance screen. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 133 On the System Info screen, tap the power unit icon to access the Power Cabinet N Info screen, and tap to display the Maintenance screen of the current power unit. Figure 4-38 Power unit maintenance Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 134 UPS reliability. Battery maintenance includes Forced Equalized Charging, Shallow Dis. Test, and Capacity Test. The next maintenance time displayed on the screen indicates the upcoming time in which to check batteries. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 135: About

    ECM is in standby state (that is, the green indicator is blinking) and then maintain the ECM. 4.1.3.5 About On the About screen, you can view the model, manufacturer, monitoring version, and power version. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 136: System Status

    On the System Status screen, you can view the data and information related to the mains input, bypass input, load, and battery by tapping corresponding icons. Figure 4-42 System status Figure 4-43 Power unit status Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 137: Common Functions

    Historical Alarms All historical alarms Historical alarms of Historical alarms of this power unit the bypass unit 4.2 WebUI 4.2.1 Login Context Internet Explorer 11 is used as the example browser. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 138 Changeme Only browses the system running information, exports (common user) system information, starts/shuts down the inverter, rectifies faults, and controls the buzzer. Other control and maintenance functions that may affect system Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 139: Monitoring Page

    When the message "Don't let this page create more messages" is displayed on the browser, if you select this option, you cannot set parameters or click Start Inverter. In this case, you need to restart the browser. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 140: Parameter Settings

    Default Value Value Range Cabinet No. Power unit number. After 1–2 power-on, the system identifies the cabinet SW terminal and updates the number automatically. This parameter is configurable only for power units. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 141 ECO function is enabled.  If this parameter is set to Disable, the system is not allowed to enter ECO mode when the D.G. supplies power to the bypass. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 142 In this mode, the total distortion of the input current waveform (THDi) is poor, but the system is stable. Weak input adaptability is suitable for mains and AC input sources. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 143 If Bus overvoltage recovery is set to Enable, the bus overvoltage alarm is Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 144 If this parameter is set to Enable, the load is light (less than 30% load), and the load rate of a certain rack is less than 10%, the system will generate a bypass current imbalance alarm and Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 145 Automatic If this parameter is set to Enable, Enable Disable, Enable equalized the UPS automatically changes charging the battery management status to equalized charge based on the Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 146 EOD restart is Enable, the UPS will restart as soon as the mains resumes. If EOD restart is disabled, clear the alarm manually or enable the restart function for the UPS. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 147 Remain. cap. An alarm is generated if this Disable Disable, Enable warning parameter is set to Enable and the remaining capacity is less Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 148: Communication Settings

    (V/cell) than this threshold, the output dry contact will output signals. 4.2.2.2 Communication Settings Figure 4-49 System communication settings Figure 4-50 Power unit communication settings Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 149: Control

    Query all historical alarms. Power unit Query historical alarms of the current power unit. Bypass unit Query historical alarms of the bypass unit. The following figure uses system query as an example. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 150: Logs

    Query and export the battery test logs of the current power unit. Bypass unit Figure 4-54 Logs 4.2.4 Config. 4.2.4.1 User Management On the home page, choose Config. > User Mgmt. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 151 If the LUI password complexity check is disabled, the user password is required to be a string of six to eight digits. If the password complexity check is enabled, the user password is required to be a string of 6–20 characters and contain at least two types of characters. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 152: Site Config

    Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be received. Configure Alarm Notification Email Address is used to configure the email address for receiving alarm emails from the monitoring system. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 153: Rccmd

    Enable upon first login. After you submit the setting, the page refreshes. The controls such as SSL Encrypted Transmission and Event Configuration will be displayed on the page, as shown in Figure 4-58. Figure 4-57 RCCMD function disabled Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 154 Disable, the RCCMD certificate controls will not be displayed on the page, as shown in Figure 4-60. If SSL Encrypted Transmission is set to Disable, a message indicating there is a risk will be displayed. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 155 The MDU supports 17 alarm events, and a maximum of 50 jobs can be added for each event, as shown in Figure 4-61. Figure 4-61 shows the buttons on the Event Configuration page, Table 4-22 describes these buttons. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 156 Button for deleting all jobs You can delete all jobs of the event by clicking this button. Figure 4-62 shows the buttons after one event is expanded and Table 4-23 describes these buttons. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 157 When adding a job, the job types to be selected are: RCCMD Shutdown, RCCMD Message, RCCMD Execute, and RCCMD TRAP. RCCMD Shutdown is selected by default. For different job types, you need to enter different contents. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 158 RCCMD Message: Specify the RCCMD client IP address, port, and message to be conveyed. The RCCMD client will receive the message. For example, enter "This is a test message". Figure 4-64 RCCMD message Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 159 UPS input voltage value (for example, single-phase: 220 V; three-phase A: 220 V, B: 220 V, C: 220 V). Table 4-24 lists the signal names that can be entered. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 160 #AUTONOMTIME Battery backup time minutes #STATUS UPS status #RUNTIME UPS operating time minutes #BATTVOLT Battery voltage #INFREQ Input frequency #BYPASSINFREQ Bypass input frequency #OUTFREQ Output frequency #CNT_PF Power supply failure times Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 161 After the certificate is uploaded successfully, click Submit. The WebUI of the MDU will restart, and the uploaded certificate will be used for communication. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 162: Managing The Ups By Using The Nms Complying With Rfc1628 Standard

    MIB file which allows the third-party NMS to manage the UPS remotely. Figure 4-68 Download the MIB The UPS-RFC1628-MIB has more alarms than RFC1628. Download the UPS-RFC1628-MIB before using. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 163: Protecting The Server By Using The Rccmd Software

    Configures and saves the address and port for receiving the shutdown command, and the message sending mechanism. For the method of installing the RCCMD client, see the manual related to the RCCMD. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 164: Rccmd Event Shutdown And Message Sending

    Step 5 On the Monitoring > Control page, start the UPS, and the inverter mode will be triggered. Send the message to the RCCMD client, indicating that the inverter is on. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 165: Ups Alive Check Function

    CS121/UPSMAN Traps. If by polling CS121/UPSMAN every x seconds... is selected as the method of detecting heartbeats, set the detection method. The default interval is 1800s and detection is performed 100 times, as shown in Figure 4-71. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 166 UPS5000-S-1200 kVA User Manual 4 User Interface Figure 4-71 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now..Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 167 UPS5000-S-1200 kVA User Manual 4 User Interface Figure 4-72 Detecting heartbeat manually Figure 4-73 Detecting heartbeat manually and successfully ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 168: Operations

    Step 3 Turn on mains input circuit breaker 1 (Q1-1), mains input circuit breaker 2 (Q1-2), and bypass input switch (Q2). After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 169: Obtaining Startup Password

    Procedure Step 1 Set the language, time, network parameters, system parameters, and battery parameters on the Settings Wizard screen. Set system parameters with caution because the settings determine normal UPS operation. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 170 Step 3 After you set parameters on the Settings Wizard screen, the system displays the Bypass mode and No battery alarms, which do not need to be handled. If there is any other alarm, you need to rectify the fault. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 171: Starting The Inverter

    Step 1 Open a browser (Internet Explorer 11 for example) and choose Tools > Internet Options. Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and then click OK. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 172 Figure 5-3 Logging in to the WebUI Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm the operation to start the inverter. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 173: Powering On Loads

    If the power units share battery strings, you need to set BCB box parameters only on the LCD of power unit 1.  If the power units do not share battery strings, you need to set BCB box parameters on the LCD of both power units. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 174: Optional) Setting Parameters For The Maintenance Bypass Unit

    The maintenance bypass cabinet has been configured. Procedure Step 1 Choose System Info > Settings > System Settings. Set Maintenance bypass cabinet to Enable. Figure 5-6 Setting parameters for the maintenance bypass cabinet Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 175: Optional) Setting Parameters For The Fan Unit

    Step 1 Shut down the inverter.  Shutting down the inverter on the LCD On the system LCD, choose Common Functions > Inv. OFF. After confirmation, the inverter is shut down. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 176 Step 4 Turn off the UPS mains input circuit breaker 1 (Q1-1), mains input circuit breaker 2 (Q1-2), bypass input switch (Q2), output circuit breaker 1 (Q5-1), and output circuit breaker 2 (Q5-2). Step 5 Turn off the upstream bypass and mains input switches for the UPS. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 177: Battery Cold Start

    Step 4 Press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 178 After the inverter starts, the UPS still works in bypass mode and the inverter is on standby. If the bypass is not normal, the inverter supplies power immediately. If the inverter is not started, the UPS may be disconnected. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 179: Testing Batteries

    Step 1 On the home screen of the power unit LCD, choose Power Unit N Info. > Maintenance > Battery Maint. Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging test. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 180: Shallow Discharge Test

    Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as required. After setting is complete, the system will perform automatic shallow discharge tests based on the settings. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 181: Capacity Test

    If the battery strings of two power units are shared, you only need to perform the capacity test for one power unit to complete all battery tests. If the battery strings are not shared, you need Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 182: Test Data Download

    5.6.4 Test Data Download Procedure Step 1 On the WebUI of the power unit, choose Query > Logs, choose logs that need to be exported from the Log drop-down list box, and click Query. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 183: Transferring To Maintenance Bypass Mode

    Step 1 Manually switch the UPS to bypass mode. Step 2 Turn on the maintenance bypass switch. After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms are displayed on the MDU. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 184: Transferring From Maintenance Bypass Mode To Normal Mode

    EPO port of the dry contact card of the bypass unit. Figure 5-16 EPO ports After you press the EPO button, the EPO and No power supplied alarms are displayed on the LCD. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 185: Clearing The Epo State

    Step 3 Check that the EPO alarm is cleared by viewing active alarms. If the system bypass input is normal, the UPS transfers to bypass mode.  Viewing active alarms on the LCD Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 186: Data Export

    You do not need to query logs. Choose Query > Logs, click Export, and save the file. Step 2 Click Query, and you can see the corresponding historical alarms. Step 3 Click Export and save the displayed web page. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 187: Setting Hibernation Mode

    Step 2 Set the module cycle hibernation period to an integer ranging from 1 to 100. The default value is 30. Figure 5-20 System settings Click Submit after setting parameters on the WebUI. ----End Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 188: Routine Maintenance

     Input voltage: 380 V AC, 400  If the input voltage is environment V AC, or 415 V AC (line abnormal, check the power grid voltage) status and input cable Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 189: Quarterly Maintenance

    Power cables and terminals The insulation layer of Replace the cables. (between the UPS and the cables is intact and terminals  Secure the output power distribution cabinet) are free from black marks terminals. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 190: Battery Maintenance

    Before installing batteries, read through the battery user manuals and pay attention to safety precautions and connection methods provided by battery manufacture. When installing and maintaining batteries, pay attention to the following points: Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 191: Precautions For Battery Maintenance

    Equalized charging voltage: battery string output terminals of battery string (2.35 V/cell ± 1%) x number of and the battery input terminals battery cells at the UPS side is greater than Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 192: Quarterly Maintenance

    2.25 V/cell ± 0.02 V/cell battery exceeds the specifications requirement, perform a complete forcible equalized charging for the battery, and check again whether the voltage is normal. 3. If the fault persists, contact Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 193: Annual Maintenance

    (A torque wrench is used for checking the torque. After checking that the battery screws meet the requirements, mark the screws for later check.) Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 194: Troubleshooting

    Close the battery switch and charge batteries until each battery has a voltage greater than the EOD voltage and 11.3 V/cell. For details about how to rectify common faults, see Table 7-1. If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical support. Table 7-1 Troubleshooting Case Symptom Possible Cause...
  • Page 195 The buzzer is activated, The bypass thyristor is Replace the bypass bypass and the Fault indicator is damaged. module. is not The bypass module Reduce the load, or normal. experiences improve ventilation. overtemperature. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 196 UPS5000-S-1200 kVA User Manual 7 Troubleshooting For details about component replacement and maintenance involved in Troubleshooting and Alarm List, consult Huawei maintenance engineers. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 197: Technical Specifications

    0%–95% RH (non-condensing) Altitude 0–1000 m The power is derated as described in IEC62040-3 when the altitude is from 1000 m to 4000 m. The upper limit of the altitude is 4000 m. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 198 35% load when the voltage is 187–80 V AC. Rated frequency 50/60 Hz Frequency range 40–70 Hz Power factor  > 0.99 (full load)  > 0.98 (half load) THDi ≤ 3% (full linear load)  Harmonic current Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 199 Cold start by pressing one If a mains outage occurs, batteries can start the UPS to supply button power to loads. Charger output power Under rated conditions, the maximum charge power of a Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 200 Load > 150% or a short circuit occurs: transfer to bypass mode after 200 ms Bypass overload capability:  The UPS runs continuously at 135% load at 30° C; generates only alarms and uses overtemperature protection at 135–150% load. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 201 The UPS runs for 100 ms when the load is greater than 1000%. Table 8-8 System electrical specifications Item Specifications Parallel reliability of Redundant parallel signals power units Parallel ECO function of Supported power units Number of parallel UPSs Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 202: Optional) Tn-C System Application

    If the TN-C system is adopted, short-circuit the input N and PE, and connect the input PE and N to the terminal on the N bar.  Recommended cable cross-sectional area: 240 mm  Recommended screw: M16 Figure 9-1 Short-circuiting the input N and PE Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 203: Alarm List

    Verify the cable connections. Reversed connections are incorrect. 1. Secure or connect the neutral wire to the 0005-1 Mains neutral Minor Cable cabinet if it is loose or disconnected. absent connections are Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 204 0021-1 Battery EOD Critical The battery If the BCB box is configured, check voltage reaches whether the BCB box trips. If it trips, close the EOD voltage the BCB box switch. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 205 2. Check whether the battery grounding  The battery failure detector is faulty by replacing it ground with a new one. monitoring 3. If no battery grounding failure detector cable is Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 206 2. Check whether the fans are functioning functioning properly. Replace the power module if properly. the fans are faulty.  The air channel for the power module is obstructed. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 207 UPS, transfer it to normal normal. mode, and replace the faulty module.  If all modules generate the alarm, open the bypass input circuit breaker. After the inverter relay is closed, close the Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 208 2. Check that the ambient temperature has properly, or not exceeded 40° C. the air 3. Check that there is no overload. channel is blocked.  The ambient temperature exceeds the upper threshold.  The load is Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 209 0584-4 The inter-rack industrial frequency synchronization cable is broken. 0085-1 Critical The EPO button Restore the EPO button status. Start the is pressed. UPS after the alarm is cleared. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 210 0337 PDC bypass Critical The bypass input The running status is displayed. No further input breaker circuit breaker measures are required. open on the PDC is OFF. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 211 2. Check that the rated voltage, rated frequency is frequency, ECO bypass voltage range, out of the and frequency range are correctly set. preset range. 3. Check that the bypass cables and circuit Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 212 1. Shut down the inverter and then close 0102-1 Maint. breaker Critical The user the maintenance circuit breaker. misoperation operation is incorrect. 2. After maintenance, open the maintenance circuit breaker and then Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 213 10 Alarm List Alarm ID Alarm Name Severity Cause Solution (Alarm ID-Cause start the inverter. 0380 In self-check Warning The inverter is in Wait until the inverter self-check is self-check. complete. Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 214: Acronyms And Abbreviations

    BBB-BOX Conformite Europeenne digital signal processing economic control operation emergency power off energy control module end of discharge International Electrotechnical Commission liquid crystal display monitor display unit Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 215 SNMP Simple Network Management Protocol THDi total distortion of the input current waveform THDv total harmonic distortion of output voltage uninterruptible power system Universal Serial Bus VRLA valve-regulated lead acid battery Issue 04 (2019-06-25) Copyright © Huawei Technologies Co., Ltd.