Huawei UPS5000-S-1200 kVA User Manual page 172

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Batt. charging
capacity
mismatch
Bat mode
shut
Backup time
warning
Remain. cap.
warning
Intelligent
hibernation
Thres. of low
batt. SOC
over dry
contact (%)
Thres. of low
batt. volt.
over dry
contact (V/
cell)
Issue 10 (2023-05-26)
Description
After this function is enabled,
an alarm is generated if the
configured battery capacity
exceeds the charging
capacity of the rack.
The UPS can automatically
power off according to the
preset shutdown delay time
only in battery mode. If the
parameter is disabled, this
function is not available.
An alarm is generated if this
parameter is set to Enable
and the backup time is less
than the warning threshold.
An alarm is generated if this
parameter is set to Enable
and the remaining capacity is
less than the warning
threshold.
If this parameter is set to
Enable, the intelligent
battery hibernation function
is enabled.
If an output dry contact is set
to Low battery SOC, and the
battery SOC is lower than
this threshold, the output dry
contact will output signals.
Lead-acid battery: If an
output dry contact is set to
Batt. Volt. Below Threshold,
and the battery voltage is
lower than this threshold, the
output dry contact will
output signals.
Lithium battery: If Batt. Volt.
Below Threshold is set for
an output dry contact and
the minimum
electrochemical voltage is
lower than the threshold, the
output dry contact will
output signals.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
75
5–80
1.70
1.70–2.10
2.80
2.60–3.20
164