Huawei UPS5000-S-1200 kVA User Manual page 146

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Battery string
sharing (only
for lead-acid
batteries)
Battery type
Battery
capacity (Ah)
Single battery
voltage (V)
Single battery
capacity (Ah)
Batteries in a
battery string
Number of
battery
strings
Installation
time
Maintenance
period (d)
Cell float
voltage (V/
cell)
Cell equalized
volt. (V/cell)
Issue 10 (2023-05-26)
Description
Two power units share
battery strings.
Type of batteries connected
to the UPS.
Capacity of lithium batteries
connected to the UPS (the
value is automatically
obtained).
Specifies the voltage of each
battery that is connected in
the battery string in series.
Specifies the capacity of each
battery that is connected in
the battery string in series.
Specifies the number of
batteries in a battery string.
Specifies the number of
battery strings connected in
parallel.
A battery maintenance
reminder is displayed when
the maintenance time
(counted from the
installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
If this parameter is set to 0,
there is no reminder.
Specifies the battery float
charging voltage.
Specifies the battery
equalized charging voltage.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable,
Enable
VRLA batt.
VRLA batt.,
lithium batt.
-
-
12V
2, 6, 12
Depends on
5–9999
the actual
model.
● 2 V battery:
● 2 V battery:
240
● 6 V battery:
● 6 V battery:
80
● 12 V
● 12 V
battery: 40
1
1–4
-
-
0
0–365
2.25
2.23 to 2.30
2.35
2.30 to 2.40
180–300
60–100
battery: 30–
50
138