Huawei UPS5000-S-1200 kVA User Manual page 147

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Dis. cur. 0.1C
EOD (V/cell)
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
EOD restart
EOD restart
delay (min)
Sched.
shallow dis.
test
Sched.
shallow dis.
test time
Sched.
shallow dis.
test interval
(d)
Issue 10 (2023-05-26)
Description
Specifies the EOD threshold
when the discharging current
is 0.1C, 0.3C, 0.5C, and 1.0C
respectively.
If the mains is not
functioning normally, the
UPS will transfer to battery
mode. When batteries reach
the EOD threshold, the
bypass is disabled, and EOD
restart is Enable, the UPS
will restart as soon as the
mains resumes.
If EOD restart is disabled,
clear the alarm manually or
enable the restart function
for the UPS.
If EOD restart is set to
Enable, the UPS starts
working after the time set for
EOD restart delay when the
input recovers from the
power failure upon EOD.
When certain conditions are
met, the charger shuts down,
and batteries supply power
to loads. The system records
the battery discharge data as
the reference for battery
capacity and lifespan.
Time for scheduled shallow
discharge test.
Interval for scheduled
shallow discharge test.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
Enable
Disable,
Enable
10
1–1440
Disable
Disable,
Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
60
30–90
139