UPS5000-S-1200 kVA
User Manual
Item
Capacitor
failure
detection
Capacitor
failure
detection
upper limit
(A)
Capacitor
failure
detection
lower limit
(A)
Bypass Settings
Item
BPM mode
upon BPM
overtemp.
BPM cur. eql.
Function
Bypass
current eql.
threshold
Issue 10 (2023-05-26)
Description
If Capacitor failure
detection is set to Enable,
the power module (power
unit) performs inverter
capacitor fault detection
based on the settings of
Capacitor failure detection
upper limit and Capacitor
failure detection lower
limit. If the power module
determines that the inverter
capacitor is faulty, it shuts
down the inverter to prevent
the fault from expanding.
-
-
Description
Specifies whether to start
bypass mode when
overtemperature occurs.
When paralleling, whether
the active current sharing is
allowed for bypass.
When BPM cur. eql.
function is set to Enable and
the maximum bypass load
rate in the parallel system
exceeds this threshold, the
bypass current equalization
function is enabled.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable,
Enable
13.0
10.0–13.0
2.5
0.0–2.5
Default Value
Value Range
Enable
Disable,
Enable
Enable
Disable,
Enable
40%
40%, 50%,
60%, 70%,
80%
160