Huawei UPS5000-S-1200 kVA User Manual page 44

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Appearance
Figure 2-16 Bypass module
(1) Run indicator
(5) Fault indicator
Table 2-3 Indicator description
Indicator
Run indicator
Alarm
indicator
Issue 10 (2023-05-26)
(2) Battery cold start
button
(6) Bypass module
Color
Green
Yellow
Copyright © Huawei Digital Power Technologies Co., Ltd.
(3) Alarm indicator
(7) Bypass control
module
Status
Description
Steady on
The system is working in bypass
mode.
Blinking at long
The bypass has no output
intervals
(blinking at 0.2 Hz, on for 2.5s
and off for 2.5s).
Blinking at short
The bypass is not configured or
intervals
the DSP software is being
upgraded (blinking at 4 Hz, on
for 0.125s and off for 0.125s).
Off
The bypass CPLD software is
being upgraded.
Steady on
A minor alarm is generated for
the bypass.
2 Product Overview
(4) Ready switch
36