Huawei UPS5000-S-1200 kVA User Manual page 82

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Prerequisites
● Before handling a busbar, wear protective gloves to avoid getting injured by
● Move a busbar with caution to avoid scratching cabinets.
● Each busbar weighs about 50 kg. Be cautious to avoid injury when moving
Preparation: two scaling ladders that are more than one meter high
At least two persons are required to carry a busbar. At least two persons are
required to hold the busbar on the top of the cabinet.
Procedure
Step 1 Remove the front panels and dustproof covers from the top of the cabinets, and
remove the connecting kits at both ends of the top of the input and output unit
and power unit 2.
Figure 3-20 Removing front panels and dustproof covers
Step 2 Install the U-shaped sealing plate component (numbered 01).
Issue 10 (2023-05-26)
NO TICE
sharp edges.
heavy objects.
When moving a busbar, hold both ends of the busbar component. It is
recommended that the soft copper bar face downward.
Do not move the busbar upward by holding the soft copper bar.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
74

Advertisement

Table of Contents
loading

Table of Contents