Huawei UPS5000-S-1200 kVA User Manual page 244

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0095-1
Insuffi.
redundancy
0096-1
ECO volt.
Abnormal
0098-1
Bypass current
not shared
0150-1
Inverter
asynchronous
Issue 10 (2023-05-26)
Severity
Minor
Minor
Minor
Minor
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cause
● The load is
excessive.
● The configured
number of
redundant
modules is
incorrect.
● The ECO
bypass voltage
or frequency is
out of the
preset range.
● The ECO
bypass voltage
or frequency
range is
incorrectly set.
● The bypass
input sequence
is reverse or
the neutral
wire is
disconnected.
● The output and
input circuit
breakers are
OFF.
● The length of
the bypass
input or output
cables is
incorrect.
● The bypass SCR
open-circuits.
● The bypass
frequency
changes fast.
● The output
frequency track
rate is
incorrectly set.
C Alarm List
Solution
1. Reduce the load.
2. Decrease the configured
number of redundant
modules.
1. Check the bypass input
voltage and frequency.
2. Check that the rated
voltage, rated frequency,
ECO bypass voltage range,
and frequency range are
correctly set.
3. Check that the bypass
cables and circuit breakers
are correctly connected.
1. Check that the output and
bypass input circuit
breakers on each rack are
ON.
2. Check that bypass input
and output power cables
on each rack meet the
length requirements.
3. Rectify any bypass SCR
open-circuit.
1. Check that the bypass
output frequency does not
change fast.
2. Check that the Output
freq. track rate is properly
set.
236