Huawei UPS5000-S-1200 kVA User Manual page 164

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Paral. sys.
hibernate
Module cycle
hiber. period
(d)
D.G. ECO
Bypass Supply
RAM
verification
Issue 10 (2023-05-26)
Description
When customer loads are
light, enable parallel
hibernation to alternate
modules in hibernation
mode, which can prolong
their service life and improve
the system efficiency.
Indicates the rotation interval
of modules in hibernation
mode. The default value is
30, which means that the
hibernating module is
rotated every 30 days.
Indicates whether ECO
bypass is allowed to supply
power in D.G. mode. When
the D.G. is connected to the
dry contact signal GEN:
● If this parameter is set to
Enable, the system can
enter ECO bypass mode
when the D.G. supplies
power to the bypass and
the ECO function is
enabled.
● If this parameter is set to
Disable, the system is not
allowed to enter ECO
mode when the D.G.
supplies power to the
bypass.
Enable or disable the
memory check function. If
this parameter is set to
Enable, the control chip RAM
working status is checked
regularly. If this parameter is
set to Disable, regular check
is disabled.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable,
Enable
30
1–100
Enable
Disable,
Enable
Disable
Disable,
Enable
156