Reduced Rate Charge Feature Configuration; Setting The Reduced Rate Charge Configuration - Webasto DVS100 Installation, Operation And Maintenance Manual

Mhe intelligent fast charging systems
Hide thumbs Also See for DVS100:
Table of Contents

Advertisement

CLEAR

5.11.7 Reduced Rate Charge Feature Configuration

The charger can be configured to allow a window of time per day to reduce the charge rate to the
connected battery. This is useful if there is a period of time when the batteries left on the charger
can charge at a slower rate to prevent heating issues or to reduce utility costs. If it is known that
during certain periods the battery will not need to charge at maximum rate then the power delivered
can be backed off by a programmable amount.
When this feature is enabled and the start and stop times are encountered, the maximum charge
rate of the battery is limited to the charge rate programmed in this feature. For example, if a
battery is connected to the charger at 11:00am, the battery capacity is 1000 amp hours, and its
start rate is 50amps/100 amp-hours, the battery will normally start charging at 500amps. If the
reduced rate feature is set to be enabled from 10:00am to 12:00pm, and the limit is 25amps/100
amp-hours, then as soon as the clock reaches 10:00 am, the current will drop from 500 to
250amps. The charging will continue with this rate limit until the window is closed at 12:00pm
when the current limit returns to 500 amps.
5.11.7.1

Setting the Reduced Rate Charge Configuration

From the "Reduced Charge Rate Setup" screen, press <enter> to display the Reduced Rate
Enable status. Press <enter> again to enable editing. Use the <up> and <down> buttons to toggle
between "ON" and "OFF" and press <enter> to accept edits. Use the <select> button to cycle
through the remaining screens. Edit the time and current limit parameters using the <enter>, <up>,
and <down> buttons. Once editing is complete, use the <clear> button repeatedly to return to the
top-level screen.
20182-W-03-01
IMPORTANT INFORMATION – SAVE THESE INSTRUCTIONS
Full Charge
Setup
ENTER
Full Charge Enable:
ON
SELECT
Full Chrg Start time
02:00
SELECT
Full Chrg End time
06:00
SELECT
Low Current Period:
0.50 Hours
SELECT
Figure 5- 18 Full Charge Setup Screens
DVS100 Installation, Operation and Maintenance
Charger Configuration
CLEAR
ENTER
Full Charge Enable:
OFF
SELECT
ENTER
Press ENTER and use the UP and
DOWN arrow buttons to set the
parameter to the appropriate value.
ENTER
Press ENTER again to accept the
selection made.
Press CLEAR to retain the original
ENTER
value
34
CLEAR
Webasto Charging Systems, Inc.