4.2
Wiring
4.2.1 General Guidelines
Check utility configuration tag on DVS100 to make sure that rated input voltage matches
local utility voltage. See Table 4-1 for details.
See Table 4-1 for Input / Output parameters.
4.2.2 Ground Wire
Green or green with a yellow stripe and attached to the compression lug provided.
4.2.3 Charging Cables / Cable Management System
To avoid shock hazard, only install cables approved by PosiCharge™ for indoor use. Use
H01N2-D (EN 50272-3) or similar type.
DANGER
4.2.4 Chassis Ground
See Table 4-1 for wiring size and additional information.
Use copper conductors only.
Minimum ground wire size is listed. Refer to local electrical codes for reference.
4.2.5 Grounding
DVS100 must be connected to an equipment-grounding conductor routed with the circuit
conductors. Connections must comply with all local codes and ordinances (EN 50178 Part
1).
The DVS100 must be grounded in accordance with the Facilities Utility grounding method.
See Table 4-1 for minimum ground wire size.
20182-W-03-01
IMPORTANT INFORMATION – SAVE THESE INSTRUCTIONS
CABLES CARRY HIGH POWER/CURRENT
Damaged Cables and/or connectors can be a serious safety hazard.
Cables must be secured with an Approved Cable Management System.
Cables are to be kept off the floor.
Failure to use a Cable Management System may invalidate Product
Warranty.
DVS100 Installation, Operation and Maintenance
7
Webasto Charging Systems, Inc.