Slot #7, Engine Interface Board (Option M4) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.1.7 Slot #7, engine interface board (option M4)

Term.
Function
98
+12/24 V DC
99
0 V DC
100
MPU input
101
MPU GND
102
A
103
B
104
C
105
A
106
B
107
C
108
A
109
B
110
C
111
Com.
112
Digital input 112
113
Digital input 113
114
Digital input 114
115
Digital input 115
116
Digital input 116
117
Digital input 117
118
Digital input 118
119
NO
120
NO
121
Com.
122
NO
123
Com.
124
NO
A1
CAN-H
A2
CAN GND
A3
CAN-L
DEIF A/S
Technical data
Description/preconfiguration
8 to 36 V DC
DC power supply
0.5 to 70 V AC/
Magnetic pickup (RPM)
10 to 10000 Hz
0(4) to 20 mA
Multi-input 1
Digital w/wire break
Preselected to digital input with wire break detection
Pt100
Pt1000
Multi-input 2
RMI
Preselected to digital input with wire break detection
0 to 40 V DC
Multi-input 3
Preselected to digital input with wire break detection
Common
Common for terminals 112 to 117
Optocoupler
Configurable
Optocoupler
Configurable
Optocoupler
Shutdown override/configurable
Optocoupler
Configurable
Optocoupler
Running feedback/configurable
Optocoupler
Configurable
Optocoupler
Emergency stop and common for 119 and 120
Relay 24 V DC/5 A
Run coil/configurable
Relay 24 V DC/5 A
Start prepare/configurable
Relay 24 V DC/5 A
Crank (starter)/configurable
Relay 24 V DC/5 A
Stop coil w/wire break/configurable
CAN bus
CAN bus J1939 engine interface (option H7)
I/O lists
Page 22 of 64