Engine - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Level 2
(OF ENABLE)
(OF) Return
(OF RETURN)
(OF) Trip
(OF TRIP)

6.2.9 Engine

Table 6.30
Crank Disconnect (CRANK DISCONN)
Level 2
Start Attempts
(START ATTEMPTS)
Disconnect on Oil Pressure Sensor
(DISCONN ON LOP SENS)
Monitor Pressure Sensor Before Crank
(MON LLOP BEF CRANK)
Pressure Sensor Monitoring Threshold
(DISCONN LOP SENS)
Monitor Pressure Switch Before Crank
(MON LOP BEF CRANK)
Disconnect on Oil Pressure Switch
(DISCONN ON LLOP SW)
Pressure Switch Transient Time
(LLOP SW TRANS TIME)
Crank Disconnect At Alt Frequency
(ALT FREQUENCY)
Crank Disconnect At Engine Speed
(ENGINE SPEED)
Disconnect On Charging Alt Voltage
(DISC ON CHG ALT VOLT)
Charging Alt Disconnect Volt Threshold
(CHG ALT THRESHOLD)
Table 6.31
Speed Monitoring (SPEED MONITOR)
Level 2
Engine Speed Sense Source
(SPEED SENSE SOURCE)
Flywheel Teeth (Magnetic Pickup)
W-Point Frequency@ 1500
Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
Under-speed Threshold
(UNDER SPEED THRESH)
Under-speed Delay
(UNDER SPEED DELAY)
USER MANUAL 4189341227A UK
Range
Disable
25.0 to 74.0 Hz
26.0 to 75.0 Hz
Range
1 to 9
Enable
Disable
Enable
Disable
0.5 to 10.0 bar
Enable
Disable
Enable
Disable
0.0 to 3.0 s
10 to 70 Hz
150 to 4000 RPM
Enable
Disable
5.0 to 30.0 V
Range
Alternator frequency
Magnetic Pickup
W-Point Frequency
1 to 300
0 to 500
Enable
Disable
0 to 3600 RPM
1 to 60 s
Page 37 of 86

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sgc 421

Table of Contents