Advertisement

Parameter
Overload Threshold
(OVERLOAD
THRESHOLD)
Overload Monitoring
Delay
(OVERLOAD MON
DELAY)
Unbalanced Load
Action
(UNBAL LOAD
ACTION)
Unbalanced Load
Threshold
(UNBAL LOAD
THRESHOLD)
Unbalanced Load
Delay
(UNBAL LOAD DELAY)
Low Load Enable
Low Load Action
Low Load Trip
Low Load Return
Low Load Delay
3.5.7

Mains

Configuration (MAINS CONFIG)
Parameter
Mains Monitoring
(MAINS MONITORING)
Mains AC System
(MAINS AC SYSTEM)
Phase Reversal
Detection
(PHASE REVERSAL
DETECT)
User manual 4189341355A EN
Range
Electrical Trip
Shutdown
10 to 200 %
1 to 600 s
None
Warning
Electrical Trip
Shutdown
Notification
5 to 200 %
1 to 600 s
Enable
Disable
None
Warning
Electrical Trip
Shutdown
Notification
1 to 99 %
2 to 100 %
1 to 3600 s
Range
Enable
Disable
Single phase
3-phase
Enable
Disable
Default
90 %
1 s
None
5 %
1 s
Not enabled
None
50 %
51 %
1 s
Default
Enabled
3-phase
Not enabled
Description
The action for overload is activated when the
load is more than this set point.
If the load is more than the set point for
overload when the time expires, the action for
overload is activated.
The action that occurs when the load is more
than the set point for unbalanced load.
The action for unbalanced load is activated
when the load is more than this set point.
If the load is more than the set point for
unbalanced load when the time expires, the
action for unbalanced load is activated.
If this parameter is enabled, the configured
action for low load is activated.
The action that occurs when low load is
detected. Low load is detected when the load is
less than the set point for low load trip (LOW
LOAD TRIP).
The set point for low load. When the load is less
than this set point, the action for low load is
activated.
If the action for low load is a warning, the
controller stops monitoring low load when the
load is more than this set point.
If the load is less than the set point for low load
when the time expires, the low load action is
activated.
Description
If this parameter is enabled, the controller
monitors the mains voltage and frequency.
Select the phase system for the mains.
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not L1-L2-L3.
Page 40 of 92