3. Operating the system

3.1

SINGLE genset controller basic actions

3.1.1

About operation of the SINGLE genset controller

A SINGLE genset controller controls and protects a prime mover and generator (that is, a genset), the generator breaker, and
optionally a mains breaker. There are no other controllers on the single-line diagram. A system can include only one SINGLE
genset controller.
Normal operation
The SINGLE genset controller is usually in LOCAL mode.
The controller can operate in REMOTE mode or LOCAL mode, and in Switchboard control.
3.1.2

SINGLE genset without mains breaker controller buttons

1
No.
Item
Notes
1
Genset
Start genset and start sequence. *
2
Breaker
Close breaker : Starts close sequence. *
3
Options
REMOTE mode : Change to REMOTE if possible. *
LOCAL mode : Change to LOCAL if possible.
NOTE
* Only in LOCAL mode. In REMOTE or Switchboard control the controller ignores the input.
OPERATOR'S MANUAL 4189341171C UK
2
3
Stop genset and stop sequence. *
Open breaker : Starts open sequence. *
Off : Controller not in REMOTE.
Green : Controller in REMOTE.
Off : Controller not in LOCAL.
Green : Controller in LOCAL.