Mains breaker is present

The ASC cannot control the mains breaker, but it is necessary to wire in position feedbacks so that the ASC knows the status of the
mains breaker. This is the case for non-power management systems (ASC is the only DEIF controller in the system).
Terminal
Function
24
Feedback for the MB open position
25
Feedback for the MB closed position
28
Common for 24 and 25
The check of the input functionality is done in the inputs/outputs page similar to the PVB. The application will contain a breaker
which is not controlled by the ASC.
COMMISSIONING GUIDELINES 4189341077D EN
Associated menus
2210 MB pos failure
2210 MB pos failure