The following shows the variable names used by the algorithm.
Name of
Description
variable
HBL
42
n1i
Round up the calculated value to the nearest integer of (ndmi + (16  n2i))  1484
When the calculation result of n1i is 2 or greater, add 1 to n2i.
n2i
■Other than  below
(RYbi + RWwbi)
RYbi: Round up the calculated value to the nearest integer of (The "RY Setting" number of points for the i-th station in which "CC-Link IE
RWwbi:Round up the calculated value to the nearest integer of (The "RWw Setting" number of points for the i-th station in which "CC-Link
■A station set to "CC-Link IE TSN Class A" and "Low-Speed" in "Communication Period Setting" for the i-th station is a CANopen
communication compatible device
n7i
ndmi
■Other than  below
(The "RY Setting" number of points for the i-th station in which "CC-Link IE TSN Class A" and "Communication Period Setting" are set to
"Low-Speed")  8 + (The "RWw Setting" number of points for the i-th station in which "CC-Link IE TSN Class A" and "Communication
Period Setting" are set to "Low-Speed")  2
■A station set to "CC-Link IE TSN Class A" and "Low-Speed" in "Communication Period Setting" for the i-th station is a CANopen
communication compatible device
n5i  2
n3i
Round up the calculated value to the nearest integer of (ndsi + (20  n4i))  1484
n4i
■Other than  below
(RXbi+RWrbi) + 1
RXbi: Round up the calculated value to the nearest integer of (The "RX Setting" number of points for the i-th station in which "CC-Link IE
RWrbi:Round up the calculated value to the nearest integer of (The "RWr Setting" number of points for the i-th station in which "CC-Link
■A station set to "CC-Link IE TSN Class A" and "Low-Speed" in "Communication Period Setting" for the i-th station is a CANopen
communication compatible device
n7i
ndsi
■Other than  below
(The "RX Setting" number of points for the i-th station in which "CC-Link IE TSN Class A" and "Communication Period Setting" are set to
"Low-Speed")  8 + (The "RWr Setting" number of points for the i-th station in which "CC-Link IE TSN Class A" and "Communication
Period Setting" are set to "Low-Speed")  2 + 8
■A station set to "CC-Link IE TSN Class A" and "Low-Speed" in "Communication Period Setting" for the i-th station is a CANopen
communication compatible device
n6i  2 + 8
n5i
A total number of device points for RPDO set in the PDO mapping whose stations are set to "CC-Link IE TSN Class A" and "Low-Speed"
in "Communication Period Setting" for the i-th station
n6i
A total number of device points for TPDO set in the PDO mapping whose station is set to "CC-Link IE TSN Class A" and "Low-Speed" in
"Communication Period Setting" for the i-th station
n7i
A total number of the main modules and extension modules whose stations are set to "CC-Link IE TSN Class A" and "Low-Speed" in
"Communication Period Setting" for the i-th station
Ex.
When using the inverter FR-E800 (RX: 32 points, RY: 32 points, RWr: 32 points, RWw: 32 points)
When 1  the number of inverters  44, n = 1
When 45  the number of inverters  88, n = 2
When 89  the number of inverters  120, n = 3
APPX
270
Appendix 6 Processing Time
TSN Class A" and "Communication Period Setting" are set to "Low-Speed")  11744
IE TSN Class A" and "Communication Period Setting" are set to "Low-Speed")  734
TSN Class A" and "Communication Period Setting" are set to "Low-Speed")  11712
IE TSN Class A" and "Communication Period Setting" are set to "Low-Speed")  732