Error
Error definition and causes
code
3013H
The value set in "Transient Transmission
Time" in "Communication Period Setting"
under "Basic Settings" of the master
station is smaller than the transient
transmission time calculated using the
number of device stations and the points
of device stations set in "Network
Configuration Settings" under "Basic
Settings".
3014H
When "Communication Mode" under
"Application Settings" of the master station
is set to "Multicast", "Communication
Period Setting" of the local station is set to
"Normal-Speed" or "Low-Speed" in the
"Network Configuration Settings" under
"Basic Settings".
3015H
Any of the items in the module which is set
as a synchronization target in "Inter-
module Synchronization Setting" in
"System Parameter" are set as follows.
• For a local station in which "Network
Synchronous Communication" in
"Network Configuration Settings" of
"Basic Settings" is set to
"Synchronous", "Communication Period
Setting" is set to the setting other than
"Basic Period".
• For the synchronization setting in
"System Parameter", a Motion module
mounted to an extension base unit is set
as a synchronization target module.
3016H
When "Network Topology" of "Basic
Settings" of the master station is set to
"Ring", for "Connection Device
Information" under "Basic Settings", "CC-
Link IE TSN Class Setting" is set to
"Mixture of CC-Link IE TSN Class B/A or
CC-Link IE TSN Class A Only".
3017H
"0.05ms Unit Setting" of "Fixed Scan
Interval Setting of Inter-module
Synchronization"" under "Inter-module
Synchronization Setting" in "System
Parameter" is set to "Not Set".
3018H
• A Motion module with the software
version in which multiple modules
cannot be set as the inter-module
synchronization target is used.
• A module which is set as a
synchronization target in "Inter-module
Synchronization Setting" in "System
Parameter" is not set as an inter-module
synchronous master.
• Two Motion modules or more are set for
"Select Inter-module Synchronization
Target Module" under "Inter-module
Synchronization Setting" in "System
Parameter".
Action
Set "Communication Period Interval Setting" and "Cyclic Transmission Time"
so that the value of "Transient Transmission Time" in "Communication
Period Setting" under "Basic Settings" of the master station is equal to or
larger than the value shown in the detailed information of module
diagnostics.
• Set "Communication Mode" in "Application Settings" of the master station
to "Unicast".
• In "Network Configuration Settings" under "Basic Settings" of the master
station, set "Communication Period Setting" of the local station to "Basic
Period".
Correct the parameters shown in the cause.
• Set "Network Topology" of "Basic Settings" of the master station to "Line/
Star".
• For "Connection Device Information" under "Basic Settings" of the master
station, set "CC-Link IE TSN Class Setting" to "CC-Link IE TSN Class B
Only".
Set "0.05ms Unit Setting" of "Fixed Scan Interval Setting of Inter-module
Synchronization" under "Inter-module Synchronization Setting" in "System
Parameter" to "Set".
• Update the Add-on baseSystem version to "1.16" or later.
• Set the module which is set as the synchronization target in "Inter-module
Synchronization Setting" in "System Parameter" as the inter-module
synchronous master.
• Set only one Motion module for "Select Inter-module Synchronization
Target Module" under "Inter-module Synchronization Setting" in "System
Parameter".
Detailed
information 1
Detailed
information 2
■
■Communication
Period Interval
Information
• Transient
Transmission Time
(Calculation value:
s)
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■Target station
information
• Station No.
• IP address
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
■
4 TROUBLESHOOTING
181
4.5 List of Error Codes
4