Item
Network
Total Device Stations
Status
(Parameter)
Total Device Stations
(Connected)
Communication Cycle
Interval Setting value
Number of Station
Errors Detected
Communication Mode
Change IP Address
Display
Network map
Data Unlinked
Selected Station Communication
Status Monitor
Operation
[Communication Test]
Test
button
Information
[Station Information
Confirmation
List] button
/Setting
Selected
[Remote Operation]
Station
button
Operation
4 TROUBLESHOOTING
150
4.3 Checking the Network Status
Description
Displays the total number of device stations set in "Network Configuration Settings" under "Basic Settings".
Displays the total number of device stations (number of device stations) that are actually connected by data link in CC-
Link IE TSN.
The communication cycle interval set in "Communication Period Setting" under "Basic Settings" of the master station is
displayed. (s unit)
Indicates the number of error stations in the displayed network.
Indicates the communication mode set in "Communication Mode" under "Application Settings" of the master station.
Allows to select from "DEC" or "HEX" for IP address display on the selected communication status monitor and
network map. (Default: Decimal)
Indicates the CC-Link IE TSN structure and the status of each station. ( Page 151 Network map)
If the status of each station is not displayed, check whether there are any overlaps of master stations.
Displays a disconnected station that has been set in "Network Configuration Settings" under "Basic Settings" but has
not yet performed data link. Reserved stations and error invalid stations are also included.
However, even if a disconnected station had performed data link, disconnected stations in the following cases are
displayed in this area.
• A station that was reconnected to a network after disconnecting/inserting the cable or powering off and on the
system, and remains disconnected
• A disconnected station with the station icon deleted in the network map by clicking the [Update] button
Displays the station No. on the station icon.
The "Other Modules" icon indicates a station that has not yet performed data link.
Icons other than the "Other Modules" icon indicate stations that had performed data link before disconnection.
For details on the displayed icon, click the [Legend] button.
Status of the station selected in "Network Status" is displayed. ( Page 153 Selected Station Communication Status
Monitor)
Performs a communication test. ( Page 154 Communication Test)
Displays information of the device stations which are performing data link in a list form. (Page 155 Station
Information List)
Performs remote operation (such as RUN, STOP, or RESET operations) to the CPU module. (Page 156 Remote