Mitsubishi Electric MELSEC iQ-R Series User Manual page 187

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
3C03H
A hardware failure has been detected.
3C0FH
A hardware failure has been detected.
3C10H
A hardware failure has been detected.
3C11H
A hardware failure has been detected.
3C13H
A hardware failure has been detected.
3C14H
A hardware failure has been detected.
3E01H
Network type of the own station is
unexpected setting.
3E02H
A time synchronization error was
detected.
3E03H
An error was detected in the memory.
3E04H
A hardware failure has been detected.
3E07H
A hardware failure has been detected.
3F00H
The firmware version is not supported by
the CPU module.
4000H
Errors detected by the CPU module ( MELSEC iQ-R CPU Module User's Manual (Application))
to
4FFFH
C011H
The port No. of the external device is not
set correctly.
C012H
The port No. used in a connection already
opened is set. (For TCP/IP)
C013H
The port No. used in a connection already
opened is set. (For UDP/IP)
C015H
The data was sent to the connected
device while the IP address setting of the
device set in the network configuration
setting was incorrect.
C017H
A connection could not be established in
the open processing.
C018H
The specified IP address of the external
device is incorrect.
Action
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the Motion module. If the same error occurs again even after taking
the above, the possible cause is a hardware failure of the Motion module.
Please consult your local Mitsubishi representative.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
Reset the CPU module, and run it again. If the same error occurs again even
after doing so, the possible cause is a hardware failure of the error module or
CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again even
after doing so, the possible cause is a hardware failure of the error module or
CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again even
after doing so, the possible cause is a hardware failure of the error module or
CPU module. Please consult your local Mitsubishi representative.
Reset the CPU module, and run it again. If the same error occurs again even
after doing so, the possible cause is a hardware failure of the error module or
CPU module. Please consult your local Mitsubishi representative.
Use a CPU module which supports Motion modules.
Correct the port No. of the external device.
Correct the port Nos. of the CC-Link IE TSN-equipped module and the
external device.
Correct the port Nos. of the CC-Link IE TSN-equipped module and the
external device.
• Correct the IP address of the connected device in the network
configuration setting.
• Check that the IP address class of the connected device is set to A, B, or
C in the network configuration setting.
• Check the operation of the external device.
• Check if the open processing has been performed in the external device.
• When a firewall is set in the external device, check if access is permitted.
• Check if the Ethernet cable is connected properly.
Correct the specified IP address of the external device.
Detailed
information 1
Detailed
information 2
4 TROUBLESHOOTING