Error
Error definition and causes
code
24C1H
An error was detected on the system bus.
24C2H
An error was detected on the system bus.
24C3H
An error was detected on the system bus.
24C6H
An error was detected on the system bus.
2600H
The cyclic processing does not finish
before the start timing for the next inter-
module synchronization cycle.
2610H
An inter-module synchronization signal
error (synchronization loss) was detected.
4 TROUBLESHOOTING
178
4.5 List of Error Codes
Action
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module, base unit, or extension cable. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module, base unit, or extension cable. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module, base unit, or extension cable. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module, base unit, or extension cable. Please consult your local Mitsubishi
representative.
• Check that the inter-module synchronous interrupt program (I44) was
written to the CPU module.
• Set the inter-module synchronization cycle to be longer than the current
value in "Fixed Scan Interval Setting of Inter-module Synchronization"
under "Inter-module Synchronization Setting" in "System Parameter".
• Make the setting value greater than the current setting for "Communication
Period Interval Setting" and "Transient Transmission Time" in
"Communication Period Setting" of the module parameter.
• If the value in 'Transient transmission additional time (calculation value)'
(SW007A) is not 0, add the value (s unit) to "Communication Period
Interval Setting" and "Transient Transmission Time".
• Reduce the number of cyclic assignment points and the number of
connected device stations, and correct the settings so that a shorter value
can be set for the communication period interval setting.
• Do not perform the online change in the CPU module.
• Take measures to reduce noise.
• Reset the CPU module, and run it again. If the same error occurs again
even after taking the above, the possible cause is a hardware failure of the
module, base unit, or extension cable. Please consult your local Mitsubishi
representative.
Detailed
information 1
Detailed
information 2
■System configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■
■System configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■
■System configuration
information
• I/O No.
• Base No.
• Slot No.
• CPU No.
■