Event
Overview
code
00C10
Own station: Data link stop (cyclic transmission stop)
00C11
Another station: Data link stop (cyclic transmission
stop)
00C21
Another station: Error occurrence
00C24
Another station: Receive frame error occurrence
00C40
Device station parameter automatic setting:
Interruption
00C41
Device station parameter automatic setting:
Parameter update interruption
00C42
Device station parameter automatic setting: System
error
00C43
Device station parameter automatic setting:
Transmission timeout
00C44
Device station parameter automatic setting: Receive
timeout
00C46
Device station parameter automatic setting: SLMP
transmission error
00C47
Device station parameter automatic setting: CPU
module access failure
00C48
Device station parameter automatic setting: No target
station parameter
00C50
Time synchronization loss
00C51
Time synchronization error
00C52
Grandmaster switching (CC-Link IE TSN device)
00C53
Grandmaster switching (general-purpose device)
00C54
Initialization failed
00C55
Message disposal
00C56
Response timeout
00C57
Message disposal
00C58
SLMP response frame disposal
00C59
Specified port No. error
00C5A
Specification IP address error
00C5B
Connection establishment failed
00C5C
TCP connection timeout
00C5D
Send processing execution disabled
00C5E
UDP/IP send failed
00C5F
TCP/IP send failed
4 TROUBLESHOOTING
202
4.7 Event List
Cause
Own station data link was stopped.
Data link of another station was stopped.
An error has occurred in another station.
A receive frame error has occurred at another station.
An abnormal response was received from the device station, and device station
parameter automatic setting processing was interrupted.
For details on device station response codes, refer to the manual for the device station
used.
An abnormal response was received from the device station, and parameter update
processing of device station parameter automatic setting was interrupted.
For details on device station response codes, refer to the manual for the device station
used.
An error occurred while the device station parameter automatic setting was executing.
Transmission timed out while communicating with the device station parameter
automatic setting.
The specified period of time expired without receiving while communicating with the
device station parameter automatic setting.
An error occurred while transmitting SLMP for the device station parameter automatic
setting.
Access to the CPU module failed during device station parameter automatic setting.
The device station parameter file targeted during device station parameter automatic
setting was not stored in the CPU module. Or the writing destination of the device station
parameters differs from the setting of the memory card parameters.
The time difference between the time notified from the grandmaster and the time of the
own station exceeded the allowable value.
The time synchronization loss occurred more than a fixed number.
The device acting as the grandmaster station was disconnected, and then the CC-Link
IE TSN device was newly selected as the grandmaster.
The device acting as the grandmaster was disconnected, and then the general-purpose
device was newly selected as the grandmaster.
A communication error occurred in the initialization processing when control
communications started.
The request was discarded because there were too many requests to be processed.
There was no response from the external device and timeout occurred.
After response timeout, the response data from the external device was received.
The SLMP response frame was disposed of due to any of the following causes.
• The request source of the received SLMP response frame is not clear.
• The received SLMP response frame has already returned an error response
according to the monitoring timeout.
• The SLMP communication load is high so that the received SLMP response frame
cannot be transferred.
There was a request for a port No. not open from the external device.
Sending was performed the a device while the "IP Address" setting of the device station
set in "Network Configuration Settings" under "Basic Settings" of the master station was
incorrect.
A connection could not be established in the open processing.
The external device does not send an ACK response in the TCP/IP communications.
• The receive buffer or send buffer is not sufficient.
• The window size of the external device is not sufficient.
Data was not sent correctly with UDP/IP due to either of the following causes.
• An error occurs in the external device.
• An error occurs in the switching hub and Ethernet cable.
• Congestion of packets on the line
Data was not sent correctly via TCP/IP due to either of following causes.
• An error occurs in the external device.
• An error occurs in the switching hub and Ethernet cable.
• Congestion of packets on the line