Error
Error definition and causes
code
D269H
The station type of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP
instruction target station is not a remote
station.
D26AH
The target station of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP
instruction does not exist.
D273H
The request data size of transient
transmission is incorrect.
D275H
Another dedicated instruction is in
execution, and the executed instruction
cannot be processed.
D2D2H
The IP address/port No. of the target
station is incorrect.
D2D3H
Send processing of the transient
transmission has failed.
D602H
Parameter error
D605H
Parameter error
D621H
Parameter error
D628H
Parameter error (station type error)
D629H
Parameter error (station No. range error)
D641H
Parameter error (IP address error)
D642H
Parameter error (gateway address setting)
D643H
Parameter error (communication cycle
setting)
4 TROUBLESHOOTING
194
4.5 List of Error Codes
Action
• Set the station type of the REMFR/REMTO/REMFRD/REMTOD/
REMFRIP/REMFRDIP/REMTOIP/REMTODIP instruction target station to
a remote station.
• Correct the network number and station number/IP address of the target
station of the dedicated instruction.
If the target station of the REMFR/REMTO/REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP instruction is disconnected, execute the
dedicated instruction again after return of the target station.
• Correct the request command at the transient request source, and retry
the operation.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Another dedicated instruction is in execution. Execute it again after a
while.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute again after correcting the port No. of the target station in the
setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Execute the instruction again after correcting the target IP address of
transient data.
• If the access destination is a module with a different network No., correct
the routing parameter setting.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the station type in the setting
data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the station No. in the setting
data so it is within 1 to 120.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the IP address in the setting
data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the gateway address setting
in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the communication cycle
setting in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Detailed
information 1
Detailed
information 2