Connected/Disconnected Module Detection

Connected device stations are detected and displayed on the "CC-Link IE TSN Configuration" window.
When the network system is started
configuration already running.
If this function is executed immediately after a device station is connected, the information of the connected device may not be
correctly read. When the information is not correctly read, retry the operation.
*1 The network parameter of the master station must be set in advance.
1.
Click the [Connected/Disconnected Module Detection] button.
2.
When the [Execute] button is clicked according to the instruction on the window, connected device stations are detected
and displayed on the "CC-Link IE TSN Configuration" window.
3.
Check items in the list of stations and change them as necessary. (Page 112 Setting items)
4.
Select [Close with Reflecting the Setting] and close the "CC-Link IE TSN Configuration" window.
Detection of connected/disconnected devices cannot be executed in the following cases.
• "Link Direct Device Setting" of the CPU parameter is not "Extended Mode (iQ-R Series Mode)".
• The actual system configuration is incorrect. (An overlapping IP address or others)
• The master station does not perform data link.
• When a CANopen supported device station is detected, PDO mapping for the corresponding station will not
be read.
*1
, it becomes easy to create parameters when changing the network system
2 PARAMETER SETTINGS
2.5 "CC-Link IE TSN Configuration" Window