No.
Name
SB00C0
Reserved station
setting status
SB00D0
Error invalid station
setting current status
SB00E8
Station type match
status of each station
SB00F0
CPU operating
status of each station
SB00F1
CPU operating
status of master
station
SB0100
CPU moderate/major
error status of each
station
SB0101
CPU moderate/major
error status of
master station
APPX
252
Appendix 3 List of Link Special Relay (SB)
Description
Stores whether a reserved station is set.
OFF: No setting
ON: Set
When this relay is turned on, the status of each station can be checked with 'Reserved
station setting status' (SW00C0 to SW00C7).
Depending on the link refresh timing, the update of 'Reserved station setting status'
(SW00C0 to SW00C7) may be offset by one sequence scan.
Stores whether an error invalid station is set.
OFF: No setting
ON: Set
When this relay is turned on, the status of each station can be checked with 'Error invalid
station setting status' (SW00D0 to SW00D7).
Depending on the link refresh timing, the update of 'Error invalid station setting status'
(SW00D0 to SW00D7) may be offset by one sequence scan.
Stores the station type match status of each station.
OFF: Station type match in all stations
ON: Station type mismatch exists
When this relay is turned on, the status of each station can be checked with 'Station type
match status' (SW00E8 to SW00EF).
Depending on the link refresh timing, the update of 'Station type match status' (SW00E8
to SW00EF) may be offset by one sequence scan.
Stores the CPU operating status of each station.
OFF: All stations in RUN or PAUSE state
ON: Station in STOP state, or station with a moderate/major error exists
When this relay is turned on, the status of each station can be checked with 'CPU
operating status of each station' (SW00F0 to SW00F7).
Depending on the link refresh timing, the update of 'CPU operating status of each station'
(SW00F0 to SW00F7) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE TSN Class A
remote station when communicating in multicast mode, "0: RUN, PAUSE" is reflected to
the CC-Link IE TSN Class A remote station.
Stores the operating status of the CPU module on the master station.
OFF: RUN, PAUSE
ON: STOP or moderate/major error
Stores the moderate/major error occurrence status of each station.
For local stations, the moderate/major error occurrence status in the CPU module of each
station are stored.
OFF: No station with a moderate/major error
ON: Station with a moderate/major error exists
When this relay is turned on, the status of each station can be checked with 'CPU
moderate/major error status of each station' (SW0100 to SW0107).
Depending on the link refresh timing, the update of 'CPU moderate/major error status of
each station' (SW0100 to SW0107) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE TSN Class A
remote station when communicating in multicast mode, "0: No moderate/major error" is
reflected to the CC-Link IE TSN Class A remote station.
When using PLCopen Motion control FB mode, if the communication cycle interval setting
is less than 125 μs, this will be fixed at "OFF: No moderate/major error".
Stores the moderate/major error occurrence status of the CPU module on the master
station.
OFF: No moderate/major error
ON: Moderate/major error