1MRS758755 C
3.1.5
Authorization settings
Table 11: Authorization settings
Parameter
Values (Range)
Remote Update
0=Disable
1=Enable
Secure Communi-
0=False
cation
1=True
Authority logging
1=None
2=Configuration
change
3=Setting group
4=Setting group,
control
5=Settings edit
6=All
Remote override
0=False
1=True
Remote viewer
Remote operator
Remote engineer
Remote adminis-
trator
Local override
0=False
1=True
Local viewer
Local operator
Local engineer
Local administrator
1
Authorization override is disabled, communication tools ask password to enter the protection
relay.
2
Authorization override is enabled, communication tools do not need password to enter the
protection relay, except for WHMI which always requires it.
3
Authorization override is disabled, LHMI password must be entered.
4
Authorization override is enabled, LHMI password is not asked.
REC615 & RER615
Technical Manual
Unit
1
2
3
4
Step
Default
0=Disable
1=True
1=None
1=True
0
0
0
0
1=True
0
0
0
0
Basic functions
Description
Remote update
Secure Communi-
cation
Authority logging
level
Disable authority
Set password
Set password
Set password
Set password
Disable authority
Set password
Set password
Set password
Set password
45