Conductors with a cross section of 0.08 to 2.5 mm² (AWG 28-12) can be con-
nected using a CAGE CLAMP
fast and maintenance free connection. To actuate CAGE CLAMP
actuation tool in the opening above the connection. Following this, enter the
conductor in the corresponding opening. The conductor is clamped securely
with the removal of the actuation tool.
Fig. 2-6: Inserting conductor end
The clamping force adjusts automatically to the cross section. The full surface
of the CAGE CLAMP
damaging it. Conductor deformation is compensated for and self-loosening is
avoided. The transition point between the conductor and the CAGE CLAMP
is protected against corrosive influences. The connection can be made quickly
and is also maintenance free, saving the costs for a periodic checking of termi-
nal connections.
Two carrier rail contacts responsible for the electrical contact between the
grounded carrier rail and the controller are fitted underneath the cou-
pler/controller.
Attention
Ensure a perfect contact point between carrier rail contacts and carrier rail.
The carrier rail must be grounded.
Modular I/O System
ETHERNET TCP/IP
connection to achieve a vibration resistant,
pressure is applied against the conductor without
The WAGO-I/O-SYSTEM 750 • 9
Electrical Installation
enter an
p0xxx06x

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-842750-342

Table of Contents