Center Tapping Adapter Cable; Figure 12: Voltage Rise For Qd-12-42-63 With End Feeding Of Ac Branch Circuit; Figure 13: Voltage Rise For Qd-12-42-63 With Center Feeding Of Ac Branch Circuit; Figure 14: Center Tapping Adapter Cable - enphase IQ8D-72-E-US Design Manual

Commercial pv design guide microinverter system
Hide thumbs Also See for IQ8D-72-E-US:
Table of Contents

Advertisement

Following Figure 12 and Figure 13 shows Voltage Rise for
last micro when AC branch circuit connection is done with
end feeding and center feeding respectively with Q-12-42-
63 landscape ballast cable.

Center Tapping Adapter Cable

The Center Tapping Adapter Cable with 300 mm (11.8
inches) length has 4 pole Link connector on one side which
should be connected to center tap connector in QD Cable
and 3 phase field wireables on other side which should be
used to make connections with extension cable to PV
© 2022 Enphase Energy Inc. All rights reserved.

Figure 12: Voltage Rise for QD-12-42-63 with End Feeding of AC Branch Circuit

Figure 13: Voltage Rise for QD-12-42-63 with Center Feeding of AC Branch Circuit

4 Pole Link QD Female Connector
(Connect to Center tap connector in
QD Cable)

Figure 14: Center Tapping Adapter Cable

The cumulative Vrise for last micro in end feeding
connection is 3.8V (1.83%) vs VRise of 1.39V (0.67%) for
center feeding connection.
Voltage Rise for Last Micro 3.8V (1.83%)
Voltage Rise for Last Micro 1.39V (0.67%)
subpanel. The 3 phase Field Wireable Connectors allows
connection for cable with wire gauge from 12AWG to
10AWG with outer diameter from 8 mm (0.3 inches) to 21
mm (0.8 inches).
300 mm
(11.8 inches)
IQ8D-DG-MKT-00397-02-EN-US-2022-06-10
Female Three Phase Field Wireable
Connector (QD-CONN-10F)
27