Following Figure 12 and Figure 13 shows Voltage Rise for
last micro when AC branch circuit connection is done with
end feeding and center feeding respectively with Q-12-42-
63 landscape ballast cable.
Center Tapping Adapter Cable
The Center Tapping Adapter Cable with 300 mm (11.8
inches) length has 4 pole Link connector on one side which
should be connected to center tap connector in QD Cable
and 3 phase field wireables on other side which should be
used to make connections with extension cable to PV
© 2022 Enphase Energy Inc. All rights reserved.
Figure 12: Voltage Rise for QD-12-42-63 with End Feeding of AC Branch Circuit
Figure 13: Voltage Rise for QD-12-42-63 with Center Feeding of AC Branch Circuit
4 Pole Link QD Female Connector
(Connect to Center tap connector in
QD Cable)
Figure 14: Center Tapping Adapter Cable
The cumulative Vrise for last micro in end feeding
connection is 3.8V (1.83%) vs VRise of 1.39V (0.67%) for
center feeding connection.
Voltage Rise for Last Micro 3.8V (1.83%)
Voltage Rise for Last Micro 1.39V (0.67%)
subpanel. The 3 phase Field Wireable Connectors allows
connection for cable with wire gauge from 12AWG to
10AWG with outer diameter from 8 mm (0.3 inches) to 21
mm (0.8 inches).
300 mm
(11.8 inches)
IQ8D-DG-MKT-00397-02-EN-US-2022-06-10
Female Three Phase Field Wireable
Connector (QD-CONN-10F)