Design Considerations For Qd Accessories; Phase Field Wireable Connectors; Qd Cable Clip; Figure 5: 3 Phase Field Wireable Connector - enphase IQ8D-72-E-US Design Manual

Commercial pv design guide microinverter system
Hide thumbs Also See for IQ8D-72-E-US:
Table of Contents

Advertisement

Design Considerations for QD Accessories

Accessories
3 Phase Field Wireable
Connectors

QD Cable Clip

Disconnect Tool
Sealing Caps
QD Cable Terminator
Center Tap Adapter Cable

3 Phase Field Wireable Connectors

When the Microinverters are located some distance from
the roof top junction box, it may be most economical to
use Raw QD Cable (without connectors) to run across
an array or to run through raceway, conduit or a chase to
another array and use 3 Phase Field Wireable Connectors
to connect. The 3 Phase Field Wireable Connectors should
be used for cables with cable gauge of 12 AWG / 10 AWG
and with maximum outer diameter of 21 mm. Please refer
to 3 Phase Field Wireable Connector Quick install guide for
installation details on
enphase.com/support.
NOTE: The five pin 3 Phase Field Wireable Connectors
includes connections for L1,L2,L3, N and PE. Do not use PE
pin when using with 4 core QD Cable.

Figure 5: 3 Phase Field Wireable Connector

© 2022 Enphase Energy Inc. All rights reserved.
SKU Number
QD-CONN-10M (Male)
QD-CONN-10F(Female)
ET-CLIP-100
QD-DISC-10
QD-SEAL-10
QD-TERM-10
QD-LINKFW-10

Table 8: QD Cable Accessories

Description
Use Field Wireable Connectors for making connections from
Raw QD Cable
Used to fasten cabling to the racking or to secure looped cabling
Disconnect tool for QD Cable connectors, DC connectors, and AC
module mount
Female Sealing cap for unused connector in QD Cable
Terminator for unused cable ends
Center Tap Adapter Cable is used for center tapping of QD Cable
in QD-12-42-63
QD Cable Clip
The Enphase QD Cable Clip (ET-CLIP-100) can manage one
or two QD Cables or Raw QD Cables to a solar mounting
rail. This clip has been evaluated with a large selection of
racking systems and works with most available rail-based
racking systems.
These clips support the cable along the rail and may be
adequate for supporting the cabling during row-to-row
transitions (depending on cable length), but additional
support may be provided from module frame clips.
Use at least one clip or other support for every 1.8 m (6
feet) of cable.

Figure 6: QD Cable Clip

IQ8D-DG-MKT-00397-02-EN-US-2022-06-10
21