Figure 43: Meter Configuration; Figure 44: Identifying Cross Talking Microinverters In The Array; Figure 45: Powerline Communication Analysis Fft Scan - enphase IQ8D-72-E-US Design Manual

Commercial pv design guide microinverter system
Hide thumbs Also See for IQ8D-72-E-US:
Table of Contents

Advertisement

05 Configure production and Consumption CTs using
the meter wizard:
A Verify that the configuration matches what is installed
(solar + load or load only).
B
Enable the meters by verifying the readings by going
through the meter wizard (required).
C While in the production meter wizard, switch OFF the
PV breakers as instructed to make sure the readings
go to zero before enabling.
D While in the consumption meter wizard, turn ON
the PV and a known load in the home to confirm
consumption rises as expected, and select the meter
location (solar + load) s
E
Refer
How do I use the meter wizard in the
Enphase Installer App to configure production and
Consumption CTs?
for commissioning the CTs
06 Troubleshooting during commissioning
A Identifying cross talking Microinverters in the array
Enlighten manager highlights the Microinverters in
array view that are communicating with multiple
Gateways at the site which are reporting or have
reported at least once in last 30 minutes during
Commissioning in Array Builder -

Figure 44: Identifying cross talking Microinverters in the array

© 2022 Enphase Energy Inc. All rights reserved.

Figure 43: Meter Configuration

B
FFT Scan (PLC Communication scan)
ITK provides a way to do the Powerline communication
analysis. This enables the user to troubleshoot and
identify conditions where the Power Line
Communications (PLC) is degraded or disrupted by
noise in the frequency band that the PLC uses for
communication. The installer can export/share the
report generated.

Figure 45: Powerline Communication Analysis FFT Scan

IQ8D-DG-MKT-00397-02-EN-US-2022-06-10
61